- ENGLISH -
- 49 -
UPS:
T
ABLES OF STATES
,
MEASUREMENTS
,
NOMINAL DATA AND COMMANDS
REGISTER
(1)
UPS - STATES
BIT
(2)
NUMBER
ADDRESS
NUMBER
ADDRESS
1
0
1
0
Test in progress[0=No / 1=YES]
2
1
3
2
Shutdown active [0=No / 1= YES]
4
3
5
4
Battery charged[0=No / 1= YES]
6
5
Battery charging[0=No / 1= YES]
7
6
Bypass bad[0=No / 1= YES]
8
7
9
8
Normal operation[0=No / 1= YES]
10
9
11
10
On bypass[0=No / 1= YES]
12
11
Battery low[0=No / 1= YES]
13
12
Battery working[0=No / 1= YES]
14
13
UPS locked[0=No / 1= YES]
15
14
Output powered[0=No / 1= YES]
16
15
2
1
17
28
16
27
Input Mains present[0=No / 1= YES]
29
28
Alarm temperature[0=No / 1= YES]
30
29
Alarm overload[0=No / 1= YES]
31
30
UPS failure[0=No / 1= YES]
32
31
3
2
33
48
32
47
4
3
49
63
48
62
Communication lost with UPS[0=No / 1= YES]
64
63
5
8
4
7
65
128
64
127
(1)
The register number
n
must be addressed
n-1
in the data packet
(2)
The bit number
n
must be addressed
n-1
in the data packet.
REGISTER
(1)
UPS - MEASUREMENTS
UNIT
NUMBER
ADDRESS
9
11
8
10
12
11
Input mains star voltage V1
V
13
12
Input mains star voltage V2
V
14
13
Input mains star voltage V3
V
15
14
Input current phase L1
0.1*A
16
15
Input current phase L2
0.1*A
17
16
Input current phase L3
0.1*A
18
17
Input frequency
0.1*Hz
19
21
18
20
22
21
Bypass mains star voltage V1
V
23
22
Bypass mains star voltage V2
V
24
23
Bypass mains star voltage V3
V
25
24
Bypass frequency
0.1*Hz
26
25
Output star voltage V1
V
27
26
Output star voltage V2
V
28
27
Output star voltage V3
V
29
31
28
30
32
31
Output current phase L1
0.1*A