- ENGLISH -
- 51 -
REGISTER
(1)
UPS
– NOMINAL DATA
UNIT
NUMBER
ADDRESS
73
77
72
76
78
77
Output nominal voltage (star)
V
79
78
Output nominal frequency
0.1*Hz
80
79
Output nominal power
100*VA
81
83
80
82
84
83
Battery nominal capacity (battery expansion included)
Ah
85
84
Battery benches
(1 or 2)
86
85
Battery type
Integer
87
112
86
111
REGISTER
(1)
UPS - COMMANDS
UNIT
NUMBER
ADDRESS
113
112
Command code
(2)
Integer
114
113
Shutdown delay time
Seconds
115
114
Restore delay time
Minutes
116
115
117
116
Command result
(3)
Integer
118
117
REGISTER
(1)
DIAGNOSTIC
UNIT
NUMBER
ADDRESS
119
118
Counter of processed correct messages
Integer
120
119
Counter of processed NOT correct messages
Integer
(1)
The register number
n
must be addressed
n-1
in the data packet.
(2)
Refer to “Command codes” paragraph
(3)
Command result = Command code if command is handled from the UPS
Command result = Command code + 100 if command is NOT handled from the UPS
Command result = 0 if Command code is wrong