Maintenance
9.2.3
Safety components
The safety components should be replaced at the end of their life
cycle indicated in the following table.
The specified life cycles do not refer to the warranty terms
indicated in the delivery or payment conditions.
Tab. O
9.3
Opening and closing the burner
Safety
component
Life cycle
Flame control
10 years or 250.000
operation cycles
Flame sensor
10 years or 250.000
operation cycles
Gas valves (solenoid)
10 years or 250.000
operation cycles
Pressure switches
10 years or 250.000
operation cycles
Pressure adjuster
15 years
Servomotor (electronic cam)
10 years or 250.000
operation cycles
Oil valve (solenoid)
10 years or 250.000
operation cycles
Oil regulator
10 years or 250.000
operation cycles
Pipes/ oil fittings (metallic)
10 years
Flexible hoses (if present)
5 years or 30.000 pressurised
cycles
Fan impeller
10 years or 500.000 start-ups
DANGER
Disconnect the electrical supply from the burner
by means of the system main switch.
DANGER
Close the fuel shut-off valve.
Wait for the components in contact with heat
sources to cool down completely.
After carrying out maintenance, cleaning or
checking operations, reassemble the cover and
all the safety and protection devices of the burner.
Summary of Contents for PRESS 450 T/N
Page 2: ...Translation of the original instructions ...
Page 35: ...33 20170392 GB Appendix Electrical panel layout 0 1 1 1 ...
Page 36: ...20170392 34 GB Appendix Electrical panel layout ...
Page 37: ...35 20170392 GB Appendix Electrical panel layout 0 1 0 2 3 2 3 ...
Page 38: ...20170392 36 GB Appendix Electrical panel layout 0 0 ...
Page 41: ......
Page 42: ......
Page 43: ......