23
20115639
GB
Start-up, calibration and operation of the burner
7.12 Programming menu
GENERAL
The programming menu can be accessed via the integrated reset
push-button, during OPERATION and in STAND-BY.
If in page menu the reset push-button is not pressed within 10
seconds the page will be automatically be exited and there will be
a green led flashing for the time set.
If the number of presses on the reset push-button exceeds the
maximum allowable, the value that stays in memory will be the
maximum one.
If the reset push-button is pressed for more than 60 seconds, a
push-button error will be displayed and the control-box will re-
start.
BLOCK DIAGRAM FOR ENTERING THE MENU
Tab. G
Function
Push-button
release time
No. of blinks of
the led per
menu page
No. of pressings
of the reset push-
button
No. of blinks of
the Led (green)
Quitting the menu
Shut-down test
5s
t < 10s
2 blinks
RED
/
none
/
none
Automatic, at the
end of the blinking
Post-
purging
10s
t < 15s
1 blink
GREEN
1 = 10 sec.
2 = 20 sec.
3 = 30 sec.
4 = 60 sec. (default)
5 = 120 sec.
6 = 0 sec. (deactivated)
1 blink
2 blinks
3 blinks
4 blinks
5 blinks
6 blinks
10 sec. after the release of
the push-button
Intermittent
operation
20s
t < 25s
3 blinks
GREEN
1 = 0 disabled
2 = 1 hour
3 = 24 hours (default)
1 blink
2 blinks
3 blinks
10 sec. after the release of
the push-button
Last lockout
memorised
25s
t < 30s
4 blinks
GREEN
/
none
Displaying the type
of lockout accord-
ing to the table sec-
tion 7.10.2
10 sec. after the release of
the push-button
S9278
OPERATION (WITH FLAME) AND STAND-BY
OPERATION INTERMITTENT
POST
OPERATION
2 RED
1 GREEN
3 GREEN
OUTLET
AUTOMATIC
10 SEC. AFTER
RELEASE
10 SEC. AFTER
RELEASE
SWITCHING OFF
PURGING
20 SEC.
LAST LOCKOUT
MEMORISED
25 SEC.
4 GREEN
10 SEC. AFTER
RELEASE
5 SEC.
10 SEC.
BURNER STATE
TYPE OF
FUNCTION
NUMBER
OUTLET
OF BLINKS
Fig. 21
PUSH-BUTTON
RELEASE TIME
OF THE LED