2902554
9
GB
TWO LINE (LIFT SYSTEM)
A)
If a two line system is required, install the By-pass
plug (4) provided. The by-pass plug is installed in
the return port (9) of the pump.
A 2.5 mm hexagonal key provided with the by pass
plug is to be used to install the plug. DO NOT use
an inch size hexagonal key, damage to the by-
pass plug may result. When operating on a two line
system, supply and return lines should be the
same diameter and both
should extend to the
same depth inside the fuel tank.
Be sure there
are no air leaks or blockages in the piping system.
Any obstructions in the return line will cause failure
of the pump shaft seal. Do not exceed the pipe
lengths indicated in the tables.
To install the by-pass plug:
1) Remove the return plug (9).
2) Install the by-pass plug (4) using the 2.5 mm
hexagonal key.
B)
Attach the two PIPE CONNECTORS (5) to the
pump SUPPLY and pump RETURN PORTS (6 and
9). Attach the required piping to these two pipe
connectors using the NPT/METRIC ADAPTERS
that are supplied with the burner.
WARNING:
- Pipe dope or Teflon tapes are NOT to be used on
any direct oil connection to the fuel pump.
- The height ‘P’ in Pipe Length Charts should not
exceed 13 feet (4 m).
- The vacuum should not exceed 11.44 inches of
mercury.
IMPORTANT:
An external, appropriately listed and certified oil
filter must be placed in the fuel line between the
fuel tank and the burner pump.
2 LINE (LIFT) SYSTEM - PIPE LENGTHS
H
3/8” OD
1/2” OD
Feet
Meters
Feet
Meters
Feet
Meters
0
0.0
115
35
330
100
1 1/2
0.5
100
30
330
100
3
1.0
80
25
330
100
5
1.5
65
20
295
90
6 1/2
2.0
50
15
230
70
9 1/2
3.0
25
8
100
30
11
3.5
20
6
65
20
D6008
H
P
H
ATTENTION:
do not exceed
pipe lengths
indicated in chart!