Installation
25
20035606
GB
4.15 Thermal relay calibration
Depending on the burner type, there are two different thermal re-
lays:
–
Electro-mechanical termal relay (used for single phase motors)
–
Electronic thermal relay (used for three phase motors)
4.15.1 Electro-mechanical thermal relay
The electro-mechanical termal relay (Fig. 24) is used to avoid dam-
age to the motor owing to a strong increase in absorption or the
lack of a phase.
For the calibration, refer to the table given in electrical layout. If the
minimum value of the scale of the thermal relay is greater than the
rating absorption of the motor, protection is still ensured.
This arises when the power supply of the motor is 400V.
To reset, in the case of an intervention of the thermal relay,
press the button “
RESET
” (Fig. 24).
The button “
STOP
” (Fig. 24) opens the NC (95-96) contact
and stops the motor.
To test the thermal relay, insert a screwdriver in the window
“
TEST
” (Fig. 25) and move it in the sense of the arrow
(towards right).
4.15.2 Electronic thermal relay
To reset, in the case of an intervention of the thermal relay,
press the button “
RESET
” (Fig. 26).
There are two different solution to test the electronic thermal relay:
Device test (Fig. 27)
Push slowly the button in the window with a little screwdriver.
Contact test NC (95-96) and NO (97-98)(Fig. 28)
Insert in the window a little screwdriver and move it in the
sense of the arrow.
WARNING
Automatic resetting can be dangerous.
This action is not provided for the burner oper-
ation.
Fig. 24
D9273
Fig. 25
D9274
Fig. 26
S8109
Fig. 27
S8111
S8111
Fig. 28
S8110
Summary of Contents for RL 300
Page 2: ......
Page 33: ...Appendix Spare parts 31 20035606 GB A Appendix Spare parts ...
Page 38: ...20035606 36 GB Appendix Electrical panel layout ...
Page 39: ...Appendix Electrical panel layout 37 20035606 GB ...
Page 41: ...Appendix Electrical panel layout 39 20035606 GB ...
Page 42: ...20035606 40 GB Appendix Electrical panel layout ...
Page 43: ...Appendix Electrical panel layout 41 20035606 GB 0 1 0 ...
Page 44: ...20035606 42 GB Appendix Electrical panel layout 0 0 0 1 0 2 0 0 0 0 0 0 0 30 3 3 0 0 1 0 ...