37
ACCESSORIES
(optional):
• OUTPUT MODULATION REGULATOR KIT
Two components should be ordered:
•
output regulator to install on the burner;
•
probe to install on the boiler.
• DEGASSING UNIT
It may occur that a certain amount of air is contained in the light oil sucked up by the pump. This air may originate from the light oil itself as a
consequence of depressurization or air leaking past imperfect seals.
In double-pipe systems, the air returns to the tank from the return pipe; in single-pipe systems, the air remains in circulation causing pressure var-
iations in the pump and burner malfunctions.
For this reason, we advise installing a degassing unit near the burner in single-pipe installations.
Degassing units are provided in two versions:
CODE
3010054
without filter
CODE
3010055
with filter
- Burner delivery
: max. 80 kg/h
- Light oil pressure
: max. 0.7 bar
- Ambient temperature
: max. 50 °C (without filter)
- Ambient temperature
: max. 40 °C (with filter)
- Light oil temperature
: max. 50 °C (without filter)
- Light oil temperature
: max. 40 °C (with filter)
- Attachment connectors
: 1/4 inch
For burner deliveries higher than 80 kg/h, install two parallel degassing units.
PARAMETER TO BE CHECKED
PROBE
POWER REGULATOR
Range
Type
Code
Type
Code
Temperature
- 100...+ 500 °C
PT 100
3010110
RWF40
3010212
Pressure
0...2,5 bar
0...16 bar
Probe with output
4...20 mA
3010213
3010214