4.9
Combustion head setting
The setting of the combustion head depends exclusively on the
maximum burner delivery at which it will be operating.
Turn screw 4)(Fig. 18) until the notch shown in diagram (Fig. 19) is
level with the front surface of flange 5)(Fig. 18).
Example:
maximum light oil delivery = 16 GPH
Diagram (Fig. 19) indicates that for a delivery of 16 GPH requires
the combustion head to be set to approx. three notches, as shown
in (Fig. 18).
Fig. 18
D462
N° Notches
Max Fuel oil delivery - GPH
D12159
Fig. 19