20168262
8
GB
Technical description of the burner
4.3
Burner categories - Countries of destination
Tab. B
4.4
Technical data
Tab. C
(1)
Reference conditions: Ambient temperature 20°C - Gas temperature 15°C - Barometric pressure 1,013 mbar - Altitude 0 m a.s.l.
(2)
Sound pressure measured in manufacturer's combustion laboratory, with burner operating on test boiler and at maximum output. The sound power
is measured with the “Free Field” method, as per EN 15036, and according to an accurate “Accuracy: Category 3” measurement, as described in
EN ISO 3746.
Country of destination
Gas category
SE - FI - AT - GR - DK - ES - GB - IT - IE - PT - IS - CH - NO
I
2H
DE
I
2ELL
NL
I
2L -
I
2E -
I
2
(43.46 - 45.3 MJ/m
3
(0°C))
FR
I
2Er
BE
I
2E(R)B
LU - PL
I
2E
Model
RLS 120/E FGR FS1
Power
(1)
Delivery
(1)
min - max
kW
kg/h
300/600 - 1200
25/50 - 101
Fuels
Light oil, max. viscosity at 20 °C: 6 mm
2
/s (1.5°E - 6 cSt)
Natural gas: G20 (methane gas)
Operation
–
Intermittent (min. 1 stop in 24 hours)
–
Oil / Gas: modulating with kit
Nozzles
number
1
Standard applications
Boilers: water, steam, diathermic oil
Room temperature
°C
0 - 40
Combustion air temperature
°C max
60
Pump
output (at 12 bar)
pressure range
fuel temperature
kg/h
bar
°C max
230
10 - 21
90
Noise levels
(2)
Sound pressure
Sound power
dB (A)
85
96
Weight
kg
100
WARNING
WARNING
To reduce the NOx of the nitric oxides in the event
of an FGR system, the maximum burner output
obtained chases based on the specific application
and within the limits agreed upon with the Riello
Technical Office.
Summary of Contents for RLS 120/E FGR
Page 2: ...Translation of the original instructions ...
Page 51: ...49 20168262 GB Appendix Electrical panel layout 01 2 3 4506 7 891 01 ...
Page 52: ...20168262 50 GB Appendix Electrical panel layout 0 1 2 2 2 0 ...
Page 54: ...20168262 52 GB Appendix Electrical panel layout 0 0 0 12 3456 7 12 3456 7 ...
Page 57: ...55 20168262 GB Appendix Electrical panel layout 0 0 1 2 3 4 5 667 8 667 2 9 63 8 63 63 3 5 ...