20096088
18
GB
Installation
4.6
Securing the burner to the boiler
Detach the combustion head from the burner (Fig. 11):
disconnect the oil pipes by unscrewing the two connectors 6);
loosen the 4 screws 3) and remove the cover 1);
disengage the swivel coupling 14) from the graduated sector;
remove the screws 2) from the slide bars 5);
remove the 2 screws 4) and pull the burner back on slide bars
5) by about 4”;
install the extension bars 31)(Fig. 5, page 10) and re-screw
the screws 2) including the safety plate 15);
disconnect the electrode wires and then pull the burner com-
pletely off the slide bars.
4.7
Electrode position
4.8
Ignition pilot adjustment
Place the pilot and electrode as shown in Fig. 13.
The pilot works correctly at pressures ranging from 3-4” WC.
Tab. L
4 "
13
L
11
12
6
14
4
5
15
2
3
1
10
8
9
7
Fig. 11
20097675
WARNING
Make sure that the electrodes are positioned as
shown in Fig. 12.
5/ 32" to 3/ 16"
3/ 32"
Fig. 12
D10108
Model
A
RLS 130/EV
3
15/64”
A
Fig. 13
D10875