Installation
19
20096088
GB
4.9
Nozzle installation
The burner complies with the emission requirements of the UL 296
standard.
In order to guarantee that emissions do not vary, recommended
and/or alternative nozzles specified by Riello in the Instruction and
warning booklet should be used.
4.9.1
Recommended nozzles
•
BERGONZO A4 45°
•
DELAVAN VARIFLO 45° and 60°
•
FLUIDICS KC2 30° and 45°
4.9.2
Nozzle assembly
In order to assemble the nozzle, proceed as follows:
remove screw 1)(Fig. 14) and extract the nozzle assembly 2);
install the nozzle 1)(Fig. 15);
fitting the wrench through the central hole in the flame stability
disk or loosen screws 1)(Fig. 16);
remove disk 2)(Fig. 16) and replace the nozzles using the
wrench 3)(Fig. 16).
WARNING
It is advisable to replace the nozzle once a year dur-
ing periodical maintenance.
CAUTION
The use of nozzles other than those specified by Ri-
ello S.p.A. and inadequate regular maintenance
may result into emission limits non-conforming to
the values set forth by the regulations in force, and
in extremely serious cases, into potential hazards to
people and objects.
The manufacturing company shall not be liable for
any such damage arising from non-observance of
the requirements contained in this manual.
WARNING
Do not use any sealing products such as gas-
kets, sealing compound, or tape.
Be careful to avoid damaging the nozzle seal-
ing seat.
The nozzles must be screwed into place tightly
but carefully.
The nozzle for low fire operation is the one
lying beneath the firing electrodes.
Make sure that the electrodes are positioned
as shown in Fig. 12.
Fig. 14
D1122
Fig. 15
D9543
Fig. 16