Installation
27
20096088
GB
4.14.1 Supply cables and external connections
passage
All the cables to be connected to the burner are fed through the
grommets. See Fig. 29.
The use of the cable grommets can take various forms. By way of
example we indicate the following mode (according to
UL795
):
1 Three phase power supply with 3/4 inch cable grommet
2 Available: single phase power supply and other devices with
1/2 inch cable grommet
3 Available: consents/safety, minimum gas pressure switch, gas
valves and other devices with 3/8 inch cable grommet
4 Available: hole for M16
5 Available for ground terminals
A
Variable speed sensor
B
Maximum gas pressure switch
C
UV sensor
D
Air servomotor
E
Fuel servomotor
F
Air pressure switch
G Oil valve
H
Oil pressure switch
I
Pump motor
4.14.2 Cable shielding
Motor supply cable
2
Single phase supply cable
3
Clamp for connection of controls cable shielding from Inverter
WARNING
It is very important to shield the motor cable 1) as
shown in Fig. 30.
It is very important to fix the cable shielding as
shown in Fig. 30.
The connection from the Inverter to LMV36...
must be done as shown in Fig. 30.
WARNING
The control panel is in compliance with UL508A.
After carrying out maintenance, cleaning or check-
ing operations, reassemble the hood and all the
safety and protection devices of the burner.