20148049
8
GB
Technical description of the burner
4.3
Burner categories - Countries of destination
Tab. B
4.4
Technical data
Tab. C
(1)
Reference conditions: Ambient temperature 20°C - Gas temperature 15°C - Barometric pressure 1013 mbar - Altitude 0 m a.s.l.
(2)
Pressure at test point 5)(Fig. 6 on page 11) with zero pressure in combustion chamber and at maximum burner output.
(3)
Sound pressure measured in manufacturer's combustion laboratory, with burner operating on test boiler and at maximum output. The sound
power is measured using the "Free Field" method, required by EN 15036 standard, and according to an “Accuracy: Category 3” measurement, as
described in EN ISO 3746.
Country of destination
Gas category
SE - FI - AT - GR - DK - ES - GB - IT - IE - PT - IS - CH - NO
I
2H
DE
I
2ELL
NL
I
2L
- I
2E
- I
2
(43.46 ÷ 45.3 MJ/m
3
(0°C))
FR
I
2Er
BE
I
2E(R)B
LU - PL
I
2E
Model
RLS 160/M MX
Flame stability disc with
round sectors 3)(Fig. 17)
Flame stability disc without
round sectors 3)(Fig. 17)
Output
(1)
Delivery
(1)
Light oil
2nd stage
min - max
kW
kg/h
965 - 1846
81 - 155
1132 - 2013
95 - 169
1st stage min
kW
kg/h
488
41
560
47
Natural
gas
2nd stage
min - max
kW
940 - 1730
940 - 1840
1st stage min
kW
300
300
Fuels
Light oil, max. viscosity at 20 °C: 6 mm
2
/s (1.5 °E - 6 cSt)
Natural gas: G20 (methane gas) - G21 - G22 - G23 - G25
Operation
–
Intermittent FS1 (min. 1 stop in 24 hours)
–
Oil: two-stage (high and low flame) and one-stage (all - nothing)
–
Gas: progressive two-stage or modulating by kit (see
ACCESSORIES)
Nozzles
number
2
Standard applications
Boilers: water, steam, diathermic oil
Ambient temperature
°C
0 - 40
Combustion air temperature
°C max
60
Pump
output (at 20 bar)
pressure range
fuel temperature
kg/h
bar
°C max
230
10 - 21
90
Noise levels
(2)
Sound pressure
Sound power
dB(A)
80.5
91.5