24
Burner goes into lockout dur-
ing operation
Faulty flame sensor
Replace worn parts
Air pressure switch faulty
Replace
Maximum gas pressure switch intervention
Adjust or replace
Lockout when the burner
stops
Permanent flame in the combustion head or flame
simulation
Eliminate permanency of flame
or replace the control box
Ignition with pulsations
Poorly adjusted head
Adjust
Ignition electrode incorrectly adjusted
Adjust it
Incorrectly adjusted fan air damper: too much air
Adjust
Output during ionisation phase is too high
Reduce
SYMBOL
PROBLEM
POSSIBLE CAUSE
RECOMMENDED REMEDY