13
20034293
GB
Technical description of the burner
4.10
Burner description
1
Flame stability disk
2
Ignition electrodes
3
Combustion head
4
Gas pressure test point and head fixing screw
5
Screw securing fan to sleeve
6
OIL/GAS selector
7
Relay
8
Slide bars for opening the burner and inspecting the com-
bustion head
9
Control box with lock-out pilot light and lock-out reset button
10 Air gate valve
11 Air inlet to fan
12 Gas input pipework
13 Gas butterfly valve
14 Screw for combustion head adjustment
15 Sleeve with flange for securing the burner to the boiler
16 Max. gas pressure switch
17 Cell UV
18 Servomotor controlling the gas butterfly valve and of air gate
valve (by means of a variable profile cam mechanism).
When the burner is not operating the air gate valve is fully
closed in order to reduce heat dispersion from the boiler due
to the flue draught which draws air from the fan suction inlet.
19 Fan motor
20 Extensions for slide bars 8)
21 Switch for: automatic - manual - off operations
Button for: increase - reduction power
22 Motor contactor and thermal cut-out with reset button
23 Bracket for mounting the power regulator RWF40
24 Terminal strip
25 Fairleads for electrical connections by installer
26 Flame inspection window
27 Minimum air pressure switch (differential operating type)
28 Pump motor
29 Pump
30 Safety solenoid valve
31 1
st
and 2
nd
stage valves
32 Air pressure test point
Two types of burner failure may occur:
Control box lock-out:
if the control box 9)(Fig. 6) pushbutton lights up, it indicates that
the burner is in lock-out. To reset, press the pushbutton.
Motor trip:
release by pressing the pushbutton on thermal relay 22)(Fig. 6).
4.11
Standard equipment
1 - Gas train flange
1 - Flange gasket
4 - Flange fixing screws (M10x40) to the butterfly valve
1 - Thermal insulation screen
4 - Screws (M16x40) to secure the burner sleeve with flange to
the boiler
2 - Hoses
2 - Nipples for hoses with gaskets
1 - Instruction booklet
1 - Spare parts list
Fig. 6
D8862
WARNING
In case of use with gas oil containing up to 10%
Bio blend, it will be essential to use flexible oil
lines suitable for bio fuel use.
Please contact Riello for further information.
Summary of Contents for RLS 250/M
Page 2: ...Original instructions ...
Page 45: ...43 20034293 GB Appendix Electrical panel layout ...
Page 46: ...20034293 44 GB Appendix Electrical panel layout ...
Page 47: ...45 20034293 GB Appendix Electrical panel layout ...
Page 48: ...20034293 46 GB Appendix Electrical panel layout ...
Page 49: ...47 20034293 GB Appendix Electrical panel layout ...
Page 51: ......