Faults - Possible causes - Solutions
GAS OPERATION
SYMBOL
(1)
FAULT
PROBABLE CAUSE
SUGGESTED REMEDY
The burner does not start
No electrical power supply
Close all switches and check con-
nections
A limiter or safety control device is open
Adjust or replace
Control box lock-out
Reset control box
Control box fuse blown
Replace
(2)
Erroneous electrical connections
Check
Defective control box
Replace
No gas supply
Open the manual valves between
meter and train
Mains gas pressure insufficient
Contact your GAS COMPANY
Minimum gas pressure switch fails to close
Adjust or replace
Air pressure switch in operating position
Adjust or replace
Contact (locking cam) of servomotor does
not operate
Adjust locking cam
or replace servomotor
The burner does not start and
a function lock-out occurs
Flame simulation
Replace control box
Defective motor command control device
Replace
Defective electrical motor
Replace
Motor protection tripped
Reset thermal cut-out
The burner starts but stops at
maximum air damper setting
Contact of servomotor does not operate
(Cam-max. opening)
Adjust cam (max.)
or replace servomotor
The burner starts and then
goes into lock-out
Air pressure switch inoperative due to insufficient air pressure:
Air pressure switch adjusted badly
Adjust or replace
Pressure switch pressure point pipe blocked
Clean
Poorly adjusted head
Adjust
Dirty fan
Clean
High negative draft in chamber
Ask our technical office
The burner starts and then
goes into lock-out
Fault in flame detection circuit
Replace control box
The burner remains in pre-
purging phase
Contact servomotor does not operate
(Minimum cam)
Adjust cam (minimum)
or replace servomotor
After pre-purge and the safety
time, the burner goes to lock-
out and the flame does not
appear
The solenoid VP1 allows little gas through
Increase
Solenoid valves VP1 or VP2 fail to open
Renew the coil or rectifier panel
Gas pressure too low
Increase pressure at governor
Ignition electrode wrongly adjusted
Adjust
Grounded electrode due to broken insulation
Replace
High voltage cable defective or grounded
Replace
High voltage cable deformed by high tempera-
ture
Replace and protect
Ignition transformer defective
Replace
Erroneous valves or transformer electrical con-
nections
Repeat connection
Defective control box
Replace
A cock down-line of the gas train is closed
Open
Air in pipework
Bleed air
The burner goes to lock-out
right after flame appearance
The solenoid VP1 or VP2 allows little gas through
Increase
Dirty flame sensor
Check, replace flame sensor
Defective connection
Check, replace flame sensor
Insufficient defection current (min.70 µA)
Measure current, replace flame
sensor
Exhausted, defective flame sensor
Replace
Max. gas pressure switch operates
Adjust or replace
Defective control box
Replace
P
1
Summary of Contents for RLS 250/M
Page 2: ...Original instructions ...
Page 45: ...43 20034293 GB Appendix Electrical panel layout ...
Page 46: ...20034293 44 GB Appendix Electrical panel layout ...
Page 47: ...45 20034293 GB Appendix Electrical panel layout ...
Page 48: ...20034293 46 GB Appendix Electrical panel layout ...
Page 49: ...47 20034293 GB Appendix Electrical panel layout ...
Page 51: ......