41
20034293
GB
Appendix - Accessories (optional)
OUTPUT POWER REGULATOR KIT RWF 40
With the modulating operation, the burner continually adapts the
power to the request for heat, ensuring great stability for the pa-
rameter controlled: temperature or pressure.
Two components should be ordered:
•
the output regulator to install on the burner
•
the probe to install on the heat generator
OUTPUT POWER REGULATOR WITH SIGNAL 4-20 mA, 0-10V
Two components should be ordered:
•
the Analogic signal converter
•
the Potentiometer
POTENTIOMETER KIT FOR THE INDICATION OF LOAD PO-
SITION
A three-pole potentiometer (1000
) can be installed to check the
position of the servomotor.
DEGASSING UNIT
It may occur that a certain amount of air is contained in the fuel
sucked up by the pump.
This air may originate from the fuel itself as a consequence of de-
pressurisation or air leaking past imperfect seals.
In double-pipe systems, the air returns to the tank from the return
pipe; in single-pipe systems, the air remains in circulation causing
pressure variations in the pump and burner malfunctions.
For this reason, we advise installing a degassing unit near the
burner in single-pipe installations.
Degassing units are provided in two versions:
CONTINUOUS VENTILATION KIT
If the burner requires continuous ventilation in the stages without
flame, a special kit is available as given in the following table.
EXTENDED HEAD KIT
“Standard head” burners can be transformed into “extended
head” versions, by using the special kit. The kits available for the
various burners, giving the original and the extended lengths, are
listed below.
SOUND PROOFING BOX
If noise emission needs reducing even further, sound-proofing
boxes is available.
SPACER KIT
If burner head penetration into the combustion chamber needs
reducing, varying thickness spacers are available, as given in the
following table.
GAS TRAINS APPROVED ACCORDING TO EN 676
Refer to the instruction manual.
A
Appendix - Accessories (optional)
Parameter to control
Probe
Output power regulator
Range
Type
Code
Type
Code
Temperature
- 100...+ 500°C
PT 100
3010110
RWF40
3010414
Pressure
0...2.5 bar
0...16 bar
Probe with output
4...20
A
3010213
3010214
Potentiometer
Analogic signal converter
Type
Code
Type
Code
ASZ...
3010416
E5202
3010415
Burner
Code
RLS 250/M MZ
3010416
Burner
Code
RLS 250/M MZ
(without filter)
20034277
RLS 250/M MZ
(with filter)
20034281
Degassing unit characteristics
Burner output
80 kg/h max
Fuel pressure
0.7 bar max
Ambient temperature
40 °C max
Fuel temperature
40 °C max
Attachment connectors
(without filter)
FF G 1/4 tank side
FM G 3/8 conic burner side
Attachment connectors
(with filter)
FF G 3/8 tank side
FM G3/8 conic burner side
Burner
Code
RLS 250/M MZ
3010094
Burner
Code
RLS 250/M MZ
3010440
Burner
Box type
Average
noise
reduction
[dB(A)]
Code
RLS 250/M MZ
C7
10
3010376
Burner
Code
RLS 250/M MZ
3000722
Summary of Contents for RLS 250/M
Page 2: ...Original instructions ...
Page 45: ...43 20034293 GB Appendix Electrical panel layout ...
Page 46: ...20034293 44 GB Appendix Electrical panel layout ...
Page 47: ...45 20034293 GB Appendix Electrical panel layout ...
Page 48: ...20034293 46 GB Appendix Electrical panel layout ...
Page 49: ...47 20034293 GB Appendix Electrical panel layout ...
Page 51: ......