Technical description of the burner
4.9
Test boiler
The firing rate was set in relation to special test boilers, according
to EN 676 regulations.
Fig. 4 indicates the diameter and length of the test combustion
chamber.
Example:
output 650 Mcal/h: diameter = 60 cm; length = 2 m.
4.9.1
Commercial boilers
The burner is suitable for operation on boilers with combustion
chambers featuring flow from the base (three flue passes) on
which the best results are obtained in terms of low NOx emis-
sions.
The maximum thickness of the boiler’s front door must not ex-
ceed 250 mm. See Fig. 5.
The burner-boiler match is assured where the boiler is EC type-
approved; for boilers and furnaces with combustion chambers
featuring dimensions differing considerably from those given in
the diagram (Fig. 4), it is advisable to perform preliminary tests.
4.9.2
Modulation ratio
The modulation ratio, determined using test boilers according to
standard (EN 676 for gas, EN 267 for light oil), is:
–
4 : 1 (gas)
–
2 : 1 (gas oil)
In case of gas operation the burner can be used with a different
modulation ratio depending on the application - contact the man-
ufacturer for further information.
D715
Fig. 4
Le
ngt
h of combust
ion
chambe
r -
mba
r
Fig. 5
250 mm MAX
D1079
Summary of Contents for RLS 250/M
Page 2: ...Original instructions ...
Page 45: ...43 20034293 GB Appendix Electrical panel layout ...
Page 46: ...20034293 44 GB Appendix Electrical panel layout ...
Page 47: ...45 20034293 GB Appendix Electrical panel layout ...
Page 48: ...20034293 46 GB Appendix Electrical panel layout ...
Page 49: ...47 20034293 GB Appendix Electrical panel layout ...
Page 51: ......