13
20010950
GB
Technical description of the burner
Electrical connection of ionization probe and flame detector
It is important to achieve practically disturbance- and loss-free
signal transmission:
• Never run the detector cables together with other cables:
– Line capacitance reduces the magnitude of the flame signal.
– Use a separate cable.
• Observe the permissible cable lengths.
• The ionization probe is not protected against electrical shock
hazard. The mainspowered ionization probe must be protect-
ed against accidental contact.
• Locate the ignition electrode and the ionization probe
such that the ignition spark cannot arc over to the ioniza-
tion probe (risk of electrical overloads).
Technical data
LMV52... basic unit
Mains voltage
AC 230 V -15 % / +10 %
Mains frequency
50 / 60 Hz ±6 %
Power consumption
< 30 W (typically)
Safety class
I, with parts according to II and III to DIN EN 60730-1
Terminal loading
‘Inputs’
Unit fuse F1 (internally)
6.3 AT
Perm. mains primary fuse (externally)
Max. 16 AT
Undervoltage
• Safety shutdown from operating position
at mains voltage
• Restart on rise in mains voltage
< AC 186 V
> AC 188 V
Oil pump / magnetic clutch (nominal voltage)
• Nominal current
• Output factor
2A
cosj > 0.4
Air pressure switch test valve (nominal voltage)
• Nominal current
• Output factor
0.5A
cosj > 0.4
Terminal loading
‘Outputs’
Total contact loading:
• Mains voltage
• Input current of unit (safety loop) total
load on contacts resulting from:
- Fan motor contactor
- Ignition transformer
- Valve
- Oil pump / magnetic clutch
AC 230 V -15 % / +10 %
Max. 5 A
Single contact loading:
Fan motor contactor (nominal voltage)
• Nominal current
• Output factor
1A
cosj > 0.4
Alarm output (nominal voltage)
• Nominal current
• Output factor
1A
cosj > 0.4
Ignition transformer (nominal voltage)
• Nominal current
• Output factor
2A
cosj > 0.2
Fuel valve gas (nominal voltage)
• Nominal current
• Output factor
2A
cosj > 0.4
Fuel valve oil (nominal voltage)
• Nominal current
• Output factor
1A
cosj > 0.4
Cable lengths
Main line
Max. 100 m (100 pF/m)
Environmental
conditions
Operation
Climatic conditions
Mechanical conditions
Temperature range
Humidity
DIN EN 60721-3-3
class 3K3
class 3M3
-20...+60 °C
< 95 % r.h.
Summary of Contents for RLS 800/EV MX
Page 2: ......
Page 38: ......
Page 75: ...37 20010950 Appendix Annexe 0 0 0 0 0 0 0 00 0 0 00 1 2 2 2 3 2 4 2 2 2 2 2 2 2 2 2 2 3 2 ...
Page 76: ...20010950 38 Appendix Annexe ...
Page 78: ...20010950 40 Appendix Annexe ...
Page 79: ...41 20010950 Appendix Annexe 0 1 1 1 ...
Page 80: ...20010950 42 Appendix Annexe 0 ...
Page 81: ...43 20010950 Appendix Annexe 0 0 1 2 2 2 3 2 4 2 2 2 2 2 2 2 52 5 5 2 2 3 2 ...
Page 82: ...20010950 44 Appendix Annexe 0 0 1 2 0 0 3 3 3 0 1 4 ...
Page 85: ...47 20010950 Appendix Annexe ৼ 0 1 1 1 1 1 2 2 2 0 2 2 2 2 2 2 2 2 2 2 2 0 2 3 ...