Technical description of the burner
3.6
Firing rates
During operation, burner output varies between:
•
MAXIMUM OUTPUT
must be selected in area
A
(Fig. 2).
•
MINIMUM OUTPUT
which must not be lower than the mini-
mum limit in the diagram.
In order to utilize also area
B
(RS 130/M) it is necessary to perform
the calibration of the combustion head as explained on page 17.
RS 50/M = 321 MBtu/hr 94 kW
NOTE:
The FIRING RATE areas given in figure (A) have been reduced
by 10% with respect to the maximum range that can be
reached. See “Procedure to refer burner operating condition
at an altitude and/or at a combustion supporter air tempera-
ture different to the standard values (328 ft above sea level, 68
°F)” to page 11 for operation at different ambient temperatures
and/or altitudes.
Model
MBtu/hr
kW
RS 70/M
512
150
RS 100/M
570
167
RS 130/M
607
178
WARNING
The firing rate area values have been obtained con-
sidering an ambient temperature of 68 °F, and an
atmospheric pressure of 394” WC and with the
combustion head adjusted as shown at page 17.
Comb
. chamb
er pr
essure
Fig. 2
“W
C
Comb. chambe
r pre
ssure
“W
C
Comb. chamber
pressur
e
“WC
RS 70/M
RS 100/M
RS 130/M