20029324
6
Technical description of the burner
3.1
Technical data
(1)
Reference conditions: Ambient temperature 68 °F (20 °C) - Barometric pressure 394” WC - Altitude 329 ft.
(2)
Pressure at test point 21) (Fig. 1), with zero pressure in the combustion chamber, with open gas ring 2) (Fig. 23, page 23) at maxi-
mum burner output
(3)
Sound pressure measured in manufacturer’s combustion laboratory, with burner operating on test boiler and at maximum rated out-
put.
*
Firing rate for C-UL/US Listing
3.2
Burner models designation
3
Technical description of the burner
Model
RS 68/E LN
RS 120/E LN
Output
(1)
High
MBtu/hr
kW
1327 - 3258
389 - 955
2282 - 4924
666 - 1443
Low
MBtu/hr
kW
570
167
1136
333
Fuel
Natural gas
• Max delivery
• Pressure at maximum delivery
(2)
natural gas
SCFH
“ WC
3258
4.60
4924
8.85
Operation
Low - high or modulating
Standard application
Boilers: water, steam, thermal oil
Ambient temperature
°F
32 - 104 (0 - 40 °C)
Combustion air temperature
°F max
140 (60 °C)
Noise levels
(3)
dB(A)
75
77
Model
Code
Code RBNA
Main Voltage
Flame safeguard
RS 68/E LN
20029006
C9342400
208-220/3/60
Burner mounted
C9342410
460/3/60
-
575/3/60
RS 120/E LN
20029007
C9343400
208-220/3/60
Burner mounted
C9343410
460/3/60
-
575/3/60
Summary of Contents for RS 120/E LN
Page 2: ......