Maintenance
6.3
Recommended preventive maintenance schedule
Operation and maintenance instructions are intended for general
applications. For specific operating and maintenance instructions,
consult the equipment manufacturer.
Tab. N
Test/Inspection
Frequency
Check gages, monitors, and indicators
DAILY
Check instrument and equipment settings
DAILY
Check burner flame
DAILY
Check igniter
WEEKLY
Check flame signal strength
WEEKLY
Check flame failure detection system
WEEKLY
Check firing rate control
WEEKLY
Make aural and visual check of pilot and main fuel valves
WEEKLY
Check flue, vent, stack, or outlet dampers
MONTHLY
Test low draft, fan air pressure, and damper position interlocks
MONTHLY
Check low-fire start interlock
MONTHLY
Test high and low gas pressure interlocks
MONTHLY
Recalibrate all indicating and recording gages
SEMI-ANNUALLY
Check flame failure detection system components
SEMI-ANNUALLY
Check firing rate control
SEMI-ANNUALLY
Check piping and wiring of all interlocks and shutoff valves
SEMI-ANNUALLY
Inspect burner components
SEMI-ANNUALLY
Flame failure detection system, test for hot refractory hold-in
ANNUALLY
Replace flame rod in accordance with manufacturer's instructions
ANNUALLY
Conduct a combustion test
ANNUALLY
Check all coils and diaphragms; test other operating parts of all safety shutoff and control valves
ANNUALLY
Test fuel valve interlock switch in accordance with manufacturer's instructions
ANNUALLY
Perform leakage test on pilot and main gas valves
ANNUALLY
Test purge air switch in accordance with manufacturer's instructions
ANNUALLY
Test low-fire start interlock in accordance with manufacturer's instructions
ANNUALLY
For gas-fired burners, check sediment trap and gas strainers
AS REQUIRED
Flame failure detection system, test for hot refractory hold in
AS REQUIRED