NORMAL OPERATION / FLAME DETECTION TIME
The control box has a further function to guarantee the correct burner operation (signal:
GREEN LED
permanently on).
To use this function, wait at least ten seconds from the burner ignition and then press the control box button for a minimum of 3 sec-
onds.
After releasing the button, the GREEN LED starts flashing as shown in the figure below.
The pulses of the LED constitute a signal spaced by approximately 3 seconds.
The number of pulses will measure the probe DETECTION TIME since the opening of gas valves, according to the following table:
ACCESSORIES
(optional):
•
RADIO DISTURBANCEPROTECTION KIT
If the burner is installed in places particularly subject to radio disturbance (emission of signals exceeding 10 V/m) owing to the presence of an
INVERTER, or in applications where the length of the thermostat connections exceeds 20 metres, a protection kit is available as an interface
between the control box and the burner.
•
OUTPUT POWER REGULATOR KIT:
Under modulating operation, the burner automatically adapts to one of an infinite number of firing rates between the low and high flame output
position, thus ensuring stable operating conditions in terms of temperature or pressure.
Two components should be ordered: • Power regulator to install to the burner; • probe to install to the boiler).
•
KIT INTERFACE ADAPTER RMG TO PC:
code
3002719
•
TUBES
KIT:
•
GAS TRAIN ACCORDING TO REGULATION EN 676 (with valves, pressure governor and filter):
see page 19.
Note:
Riello S.p.a. declines all responsibility for the addition of safety devices not provided for herein.
SIGNAL
FLAME DETECTION TIME
This is updated in every burner start-up.
Once read, the burner repeats the start-up cycle by briefly
pressing the control box button.
WARNING
If the result is > 2s, ignition will be retarded.
Check the adjustment of the hydraulic brake of the gas
valve, the air damper and the combustion head adjustment.
1 blink
0.4s
2 blinks
0.8s
6 blinks
2.8s
Burner
RS 68/M BLU - RS 120/M BLU
Code
3010386
PARAMETER TO BE CHECKED
PROBE
POWER REGULATOR
Range
Type
Code
Type
Code
Temperature
- 100...+ 500°C
PT 100
3010110
RWF50
RWF55
20082208
20099657
Pressure
0...2,5 bar
0...16 bar
Output probe
4...20 mA
3010213
3010214
Burner
RS 68/M BLU
RS 120/M BLU
Code
3010247
3010248
GB
GREEN LED on
wait at least 10s
Press button
for > 3s
signal
signal
Interval
3s