TECHNICAL DATA
(1) Reference conditions: Ambient temperature 20°C - Barometric pressure 1000 mbar - Altitude 100 m s.l.m.
(2) Pressure at test point 16)(A)p.8, with zero pressure in the combustion chambre, with open gas ring 2)(B)p.16 an maximum burner output.
(2) Sound pressure measured in manufacturer's combustion laboratory, with burner operating on test boiler and at maximum rated output. The
sound power is measured with the “Free Field” method, as per EN 15036, and according to an “Accuracy: Category 3” measuring accuracy,
as set out in EN ISO 3746.
ELECTRICAL DATA
Motor IE2
VARIANTS
MODEL
RS 68/M BLU
RS 120/M BLU
TYPE
846 T
847 T
OUTPUT
(1)
MAX.
kW
350 - 860
301 - 740
600 - 1300
516 - 1118
Mcal/h
MIN.
kW
150
130
300
258
Mcal/h
FUEL
NATURAL GAS: G20 - G21 - G22 - G23 - G25
G20
G25
G20
G25
- Net calorific value
kWh/Sm
3
Mcal/Sm
3
9.45
8.6
8.13
7.4
9.45
8.6
8.13
7.4
- Absolute density
kg/Sm
3
0.71
0.78
0.71
0.78
- Max. delivery
Sm
3
/h
86
100
130
151
- Pressure at max. delivery
(2)
mbar
11.7
17.3
22.5
33.3
OPERATION
• On-Off (1 stop min each 24 hours).
• Progressive two-stage or modulating by kit (see ACCESSOIRES).
STANDARD APPLICATIONS
Boilers: water, steam, diathermic oil
AMBIENT TEMPERATUR
°C
0 - 40
COMBUSTION AIR TEMPERATURE
°C max
60
IN CONFORMITY WITH DIRECTIVES
2009/142 - 2006/42 - 2014/35 - 2014/30
NOISE LEVELS
(3)
Sound pressure
Sound power
dBA
77
88
78.5
89.5
APPROVAL
CE
0085 BM 0452
MODEL
RS 68/M BLU
RS 120/M BLU
ELECTRICAL SUPPLY
V
Hz
230 - 400 with neutral ~ +/-10%
50 - three-phase
ELECTRIC MOTOR
rpm
W
V
A
2860
1500
230 - 400
5.5 - 3.4
2860
2200
230 - 400
7.9 - 4.6
IGNITION TRANSFORMER
V1 - V2
I1 - I2
230 V - 1 x 8 kV
1 A - 20 mA
ELECTRICAL POWER CONSUMPTION
W max
1500
2200
ELECTRICAL PROTECTION
IP 44
Country
Category
SE-FI-AT-GR-DK-ES-GB-IT-IE-PT-IS-CH-NO
DE
NL
FR
BE
LU - PL
I
2H
I
2ELL
I
2L -
I
2E -
I
2
(43.46 ÷ 45.3 MJ/m3 (0°C))
I
2Er
I
2E(R)B
I
2E
Burner model
Blast tube lenght mm
RS 68/M BLU
RS 120/M BLU
255 - 390
GB