Faults - Probable causes - Solutions
111
0
Low level of power supply
Insufficient mains voltage.
Conversion of the diagnostic code
Voltage value (230 V AC : 1,683)
112
0
Reset power supply voltage
Error code for the carrying out of a reset in the event of power
supply restoration (absence of error)
113
#
Mains voltage supervision internal error
Carry out a reset; if the error arises repeatedly, replace the
control box
115
#
Control box meter internal error
116
0
Life cycle of the control box in the critical interval
(250,000 Start ups)
The envisaged life cycle of the control box has been exceeded.
Replace it.
117
0
Life cycle of the control box exceeded
The switch-off threshold has been reached.
120
0
Interruption of fuel limiting meter input
Too many disturbance impulses on the input of the fuel meter.
Improve the electromagnetic compatibility.
121 ÷ 124
#
EEPROM access internal error
Carry out a reset, repeat and check the last setting of the
parameters. Restore the group of parameters: if the error arises
repeatedly, replace the control box.
125
#
EEPROM reading access internal error
Carry out a reset, repeat and check the last setting of the
parameters. If the error arises repeatedly, replace the control
box.
126
#
EEPROM writing access internal error
Carry out a reset, repeat and check the last setting of the
parameters. If the error arises repeatedly, replace the control
box.
127
#
EEPROM access internal error
Carry out a reset, repeat and check the last setting of the
parameters. Restore the group of parameters: if the error arises
repeatedly, replace the control box.
128
0
EEPROM access internal error - synchronisation
during the initialisation
Perform a reset; if the error arises repeatedly, replace the
control box.
129
#
EEPROM access internal error – command
synchronisation
Carry out a reset, repeat and check the last setting of the
parameters. If the error arises repeatedly, replace the control
box.
130
#
EEPROM access internal error - time-out
Carry out a reset, repeat and check the last setting of the
parameters. If the error arises repeatedly, replace the control
box.
131
#
EEPROM access internal error - page interrupted
Carry out a reset, repeat and check the last setting of the
parameters. If the error arises repeatedly, replace the control
box.
132
#
EEPROM register initialisation internal error
Perform a reset; if the error arises repeatedly, replace the
control box.
133 ÷ 135
#
EEPROM access internal error – request
synchronisation
Carry out a reset, repeat and check the last setting of the
parameters. If the error arises repeatedly, replace the control
box.
136
1
Restoration started
The restoration of a backup has been started (no error)
137
#
Internal error – backup / restoration
157 (-99)
Restoration – OK, but backup < compared with set data of
current system
Restoration successful, but the backup data installed are fewer
than those currently present in the system.
239 (-17)
Backup - logging of the backup on RDI21… failed
Perform the reset and repeat backup
240 (-16)
Reset - no backup in RDI21…
No backup in RDI21…
241 (-15)
Reset - Interruptions relating to impracticable ASN
The backup has an impracticable ASN and cannot reset the
unit
242 (-14)
Backup – the backup carried out is contradictory
The backup is irregular and cannot be transferred again
243 (-13)
Backup – the data comparison between the internal
microprocessors is irregular
Repeat the reset and backup
244 (-12)
The backup data are incompatible
The backup data are incompatible with the current version of
the software; the restoration is not possible
245 (-11)
Error in access to the parameter Restore_Complete
Repeat the reset and backup
246 (-10)
Restoration – time-out during logging in EEPROM
Repeat the reset and backup
247 (-9)
The data received are contradictory
The series of backup data is not valid; restoration is not
possible
248 (-8)
The restoration cannot currently be carried out
Repeat the reset and backup
249 (-7)
Restoration – interruption caused by inadequate
identification of the burner
The backup has an inadequate identification of the burner and
must not be transferred to the control box
250 (-6)
Backup – the CRC of a page is not correct
The series of backup data is not valid; restoration is not
possible
251 (-5)
Backup – the identification of the burner is not defined
Define the identification of the burner and repeat the backup
252 (-4)
After restoration, the pages are still in INTERRUPTION
Repeat the reset and backup
253 (-3)
The restoration cannot currently be carried out
Repeat the reset and backup
Error
code
Diagnostic code
Meaning of the REC 27.100A2 system
Recommended measures
Summary of Contents for RS 25/E BLU Series
Page 2: ...Translation of the original instructions...
Page 65: ...63 20068118 GB Appendix Electrical panel layout RS 25 E BLU...
Page 66: ...20068118 64 GB Appendix Electrical panel layout RS 35 E BLU...
Page 67: ...65 20068118 GB Appendix Electrical panel layout RS 35 E BLU 3Ph...
Page 68: ...20068118 66 GB Appendix Electrical panel layout RS 25 35 E BLU...
Page 69: ...67 20068118 GB Appendix Electrical panel layout RS 35 E BLU 3Ph...
Page 70: ...20068118 68 GB Appendix Electrical panel layout...
Page 71: ...69 20068118 GB Appendix Electrical panel layout...
Page 72: ...20068118 70 GB Appendix Electrical panel layout...
Page 73: ...71 20068118 GB Appendix Electrical panel layout...
Page 75: ......