background image

12

NOTE

The servomotor follows the adjustment of cam
III only when the angle of the cam is reduced. If
it is necessary to increase the angle of the cam,
you must first increase the angle of the servo-
motor by means of the “output increase” key,
then increase the angle of cam III, and finally
bring the servomotor to the position of MIN out-
put, with the “output reduction” key.

If it is necessary to adjust cam III, remove the
cover 1) (inserted with a trigger catch, as indi-
cated in fig. (B), extract the special key 2) from
inside, and insert it in the notch of cam III.

Adjustment of air delivery
Progressively adjust the starting profile of cam
4)(A) by turning the screws working through the
access hole 6)(A). It is preferable not to turn the
first screw since this is used to set the air
damper to its fully closed position.

2 - MAX. OUTPUT

Max. output of the burner must be set within the
firing rate range shown on page 5.
In the above description, we left the burner
switched on, working at MIN output. Now press
the button 2)(A)p.11 “output increase”, and keep
it pressed until the servomotor has opened the
air damper and the gas butterfly valve at 90°.
Adjusting gas delivery
Measure the gas delivery at the meter.
As a general rule, it can be seen from the table
on page 6, just read the gas pressure on the
pressure gauge, see fig.(C)p.10, and follow the
indications given on page 6.
- If delivery needs to be reduced, diminish out-

let gas pressure and, if it is already very low,
slightly close adjustment valve VR.

- If delivery needs to be increased, increase

outlet gas pressure.

Adjustment of air delivery
Progressively adjust the end profile of cam 4)(A)
by turning the cam adjustment screws as they
appear through the access opening 6)(A).
- Turn the screws clockwise to increase air

delivery.

- Turn the screws anti-clockwise to reduce air
delivery.

 3 - INTERMEDIATE OUTPUTS

Adjusting gas delivery
No adjustment of gas delivery is required.

Adjustment of air delivery
Press the key 2)(A)p.11 “output increase” a little
so that a new screw 5)(A) appears in the open-
ing 6)(A). Adjust it until optimal combustion is
obtained. Proceed in the same way with the
other screws.
Take care that the cam profile variation is pro-
gressive.
Switch the burner off with the switch 1)(A)p.11.
Release the variable profile cam by putting the
servomotor slot 2)(A) in a vertical position and
check more than once, rotating the cam forward
and backward by hand, that the movement is
soft and smooth, without sticking.
As far as is possible, try not to move those
screws at the ends of the cam that were previ-
ously adjusted for the opening of the air damper
to MAX and MIN output.

NOTE

Once you have finished adjusting outputs MAX -
MIN - INTERMEDIATE, check ignition once
again: noise emission at this stage must be
identical to the following stage of operation. If
you notice any sign of pulsations, reduce the
ignition stage delivery.

(A)

(B)

D518

D793

1 Servomotor

2

Constraint /

Release of cam 4

3 Cam cover

4 Variable profile cam

5 Screws for adjusting the variable profile

6 Slit to access the screws 5

7 Index of graduated sector 8

8 Gas butterfly valve graduated sector

Summary of Contents for RS 25/M BLU

Page 1: ...de aire soplado Queimadores a g s com ar insuflado Progressive two stage or modulating operation Funcionamiento a dos llamas progresivas o modulante Funcionamento a duas chamas progressivas ou modula...

Page 2: ...h the burner is an integral and essential part of the product and must not be sep arated from it it must therefore be kept carefully for any necessary consultation and must accompany the burner even i...

Page 3: ...rs com Distributed by RIELLO NV Ninovesteenweg 198 9320 Erembodegem Tel 053 769 030 Fax 053 789 440 e mail info riello be URL www riello be It is hereby certified that the apparatuses specified below...

Page 4: ...0 78 max delivery Sm3 h 39 45 51 59 51 59 pressure at max delivery 2 mbar 15 6 21 8 14 1 24 7 14 1 24 7 OPERATION On Off 1 stop min each 24 hours Progressive two stage or modulating by kit see ACCESSO...

Page 5: ...25 M BLU RS 35 M BLU Output kW 80 125 370 kW 120 200 470 kW Blast tube length mm 230 365 230 365 Code 3010423 3010424 OUTPUT POWER REGULATOR KIT RWF50 SIGNAL CONVERTER KIT 4 20 mA 0 10V Two component...

Page 6: ...Guide extensions long head version 26 4 pole socket cover see electrical panel appendix Two types of burner failure may occur CONTROL BOX LOCKOUT if the control box 21 A pushbutton lights up it indica...

Page 7: ...indicates the diameter and length of the test combustion chamber Example Output 350 Mcal h diameter 50 cm length 1 5 m COMMERCIAL BOILERS The burner boiler combination does not pose any problems if th...

Page 8: ...onds to 9 3 mbar pressure column 1 This value serves as a rough guide the effective output must be measured at the gas meter To calculate the required gas pressure at test point 1 B set the maximum ou...

Page 9: ...promise the extraction of the blast tube For boilers with a water cooled frontpiece a heat resistant cover is not necessary 11 12 C unless expressly requested from the boiler man ufacturer FIXING THE...

Page 10: ...needs a particular setup it is possible to modify the central air delivery using the ring nut 4 A up to the notch indicated in diagram C In order to carry out this operation unscrew the screws 5 A and...

Page 11: ...detection device supplied as an accessory or incorporated based on the gas train code In compliance with the EN 676 standard the leak detection control is compul sory for burners with maximum outputs...

Page 12: ...tion When the burner is at max output the gas butterfly valve must be fully open 90 Cam I I 0 Limits rotation toward the minimum position When the burner is shut down the air damper and gas butterfly...

Page 13: ...elapsed Perform 10 ignitions with consecutive lock outs Read on the meter the quantity of gas burned This quantity must be equal to or lower than the quantity given by the formula for ts 3s Vg volume...

Page 14: ...y low slightly close adjustment valve VR If delivery needs to be increased increase outlet gas pressure Adjustment of air delivery Progressively adjust the end profile of cam 4 A by turning the cam ad...

Page 15: ...pression in the combustion chamber during the pre purging phase does not allow the air pressure switch to commute commutation can be obtained by applying a second tube between the air pres sure switch...

Page 16: ...hat controls the pressure or the temperature in the boiler point C The electrical control box still continues to check the presence of the flame and the correct position of the air and gas pressure sw...

Page 17: ...re should be exercised during maintenance Gas leaks Make sure there are no gas leaks on the pipe work between the gas meter and the burner Gas filter Substitute the gas filter when dirty see train ins...

Page 18: ...ong head models unscrew the exten sions and reposition them in the appropriate space tighten the screws to the guides 2 C p 7 Reposition the hood 2 and fix with the screw 1 SWITCHBOARD MAINTENANCE If...

Page 19: ...l box serial number etc To display the diagnostic proceed as follows Keep the button pressed for more than 3 seconds from when the red LED burner lockout switches on The end of the operation will be s...

Page 20: ...nt ionisation less than 5 A Check probe position 28 Earth probe Withdraw or replace cable 29 Burner poorly grounded Check grounding 30 Phase and neutral connections inverted Invert them 31 Defective f...

Reviews: