background image

17

BURNER START-UP CYCLE DIAGNOSTICS

During start-up, the indications are explained in the following table: 

RESET OF CONTROL BOX AND DIAGNOSTICS USE

The control box supplied features a diagnostics function, through which any causes of malfunctioning can be easily identified (indicator: 

RED LED

signal).
To use this function, wait at least 10 seconds from when the safety condition has been set (

lockout

), then press the reset button. 

The control box generates a sequence of led pulses (1 second apart) that is repeated at constant intervals of 3 seconds. 
Once the number of LED pulses has been visualised, and the possible cause identified, it is necessary to reset the system, keeping the button
pressed for 1-3 seconds.  

Below, a list of the possible methodologies for carrying out the resetting of the control box and for using the diagnostics.

CONTROL BOX RESET 

To reset the control box, proceed as follows:
-

Press and hold the button for 1-3 seconds. 
The burner starts up again, 2 seconds after the button is released. If the burner does not restart, make sure the limit thermostat is closed.

VISUAL DIAGNOSTICS 

Indicate the type of burner fault that leads to the lockout.
To display the diagnostic, proceed as follows:
-

Keep the button pressed for more than 3 seconds from when the red LED (burner lockout) switches on.
The end of the operation will be shown by a yellow led pulse.
Release the button when you see the flashing. The number of flashes indicates the cause of the malfunctioning, on the basis of the code
given in the table on page 18.

SOFTWARE DIAGNOSTICS

Gives an analysis of the life of the burner, through optical connections with a PC showing the working hours, number and types of lockout, control
box serial number etc.
To display the diagnostic, proceed as follows:
-

Keep the button pressed for more than 3 seconds from when the red LED (burner lockout) switches on. 
The end of the operation will be shown by a yellow led pulse. 
Release the button for 1 second, then press it again for more than 3 seconds, until you see another yellow flash.
When you release the button, the red led will flash intermittently with high frequency: only then is it possible to insert the optical connection.

When the operation is completed, it is necessary to reset the start-up condition of the control box, using the reset procedure described above. 

The sequence of led pulses issued by the control box identifies the possible types of fault, which are listed in the table on page 18.

 COLOUR CODE TABLE 

Sequences

Colour code

Pre-purging

Ignition phase

Operation, flame OK

Operation with weak flame signal

Electrical supply lower than  ~ 170V

Lockout

Extraneous light

Key to layout:

Off

Yellow

Green

Red

In the event of a burner lockout, more than two consecutive burner reset operations could cause damage to the installation. On the
third lockout, contact the Aftersales Service.

If further lockouts or burner faults occur, interventions must only be made by qualified, authorised personnel (as indicated in this man-
ual, and in compliance with the laws and regulations currently in force).

PRESSURE ON THE BUTTON

STATE OF CONTROL BOX

From 1 to 3 seconds

Reset of the control box without visualisation of the visual diagnostics.

More than 3 seconds

Visual diagnostics of the lockout condition:
(led flashes at 1 second intervals).

More than 3 seconds, starting from the condition
of visual diagnostics

Software diagnostics, with the help of optical interface and PC 
(possibility to visualise the working hours, irregularities, etc.)

Press reset

for > 3 s

3 s

led pulses

led pulses

RED LED illuminated

wait at least 10s

Interval

Lockout

Summary of Contents for RS 25/M BLU

Page 1: ...de aire soplado Queimadores a g s com ar insuflado Progressive two stage or modulating operation Funcionamiento a dos llamas progresivas o modulante Funcionamento a duas chamas progressivas ou modula...

Page 2: ...h the burner is an integral and essential part of the product and must not be sep arated from it it must therefore be kept carefully for any necessary consultation and must accompany the burner even i...

Page 3: ...rs com Distributed by RIELLO NV Ninovesteenweg 198 9320 Erembodegem Tel 053 769 030 Fax 053 789 440 e mail info riello be URL www riello be It is hereby certified that the apparatuses specified below...

Page 4: ...0 78 max delivery Sm3 h 39 45 51 59 51 59 pressure at max delivery 2 mbar 15 6 21 8 14 1 24 7 14 1 24 7 OPERATION On Off 1 stop min each 24 hours Progressive two stage or modulating by kit see ACCESSO...

Page 5: ...25 M BLU RS 35 M BLU Output kW 80 125 370 kW 120 200 470 kW Blast tube length mm 230 365 230 365 Code 3010423 3010424 OUTPUT POWER REGULATOR KIT RWF50 SIGNAL CONVERTER KIT 4 20 mA 0 10V Two component...

Page 6: ...Guide extensions long head version 26 4 pole socket cover see electrical panel appendix Two types of burner failure may occur CONTROL BOX LOCKOUT if the control box 21 A pushbutton lights up it indica...

Page 7: ...indicates the diameter and length of the test combustion chamber Example Output 350 Mcal h diameter 50 cm length 1 5 m COMMERCIAL BOILERS The burner boiler combination does not pose any problems if th...

Page 8: ...onds to 9 3 mbar pressure column 1 This value serves as a rough guide the effective output must be measured at the gas meter To calculate the required gas pressure at test point 1 B set the maximum ou...

Page 9: ...promise the extraction of the blast tube For boilers with a water cooled frontpiece a heat resistant cover is not necessary 11 12 C unless expressly requested from the boiler man ufacturer FIXING THE...

Page 10: ...needs a particular setup it is possible to modify the central air delivery using the ring nut 4 A up to the notch indicated in diagram C In order to carry out this operation unscrew the screws 5 A and...

Page 11: ...detection device supplied as an accessory or incorporated based on the gas train code In compliance with the EN 676 standard the leak detection control is compul sory for burners with maximum outputs...

Page 12: ...tion When the burner is at max output the gas butterfly valve must be fully open 90 Cam I I 0 Limits rotation toward the minimum position When the burner is shut down the air damper and gas butterfly...

Page 13: ...elapsed Perform 10 ignitions with consecutive lock outs Read on the meter the quantity of gas burned This quantity must be equal to or lower than the quantity given by the formula for ts 3s Vg volume...

Page 14: ...y low slightly close adjustment valve VR If delivery needs to be increased increase outlet gas pressure Adjustment of air delivery Progressively adjust the end profile of cam 4 A by turning the cam ad...

Page 15: ...pression in the combustion chamber during the pre purging phase does not allow the air pressure switch to commute commutation can be obtained by applying a second tube between the air pres sure switch...

Page 16: ...hat controls the pressure or the temperature in the boiler point C The electrical control box still continues to check the presence of the flame and the correct position of the air and gas pressure sw...

Page 17: ...re should be exercised during maintenance Gas leaks Make sure there are no gas leaks on the pipe work between the gas meter and the burner Gas filter Substitute the gas filter when dirty see train ins...

Page 18: ...ong head models unscrew the exten sions and reposition them in the appropriate space tighten the screws to the guides 2 C p 7 Reposition the hood 2 and fix with the screw 1 SWITCHBOARD MAINTENANCE If...

Page 19: ...l box serial number etc To display the diagnostic proceed as follows Keep the button pressed for more than 3 seconds from when the red LED burner lockout switches on The end of the operation will be s...

Page 20: ...nt ionisation less than 5 A Check probe position 28 Earth probe Withdraw or replace cable 29 Burner poorly grounded Check grounding 30 Phase and neutral connections inverted Invert them 31 Defective f...

Reviews: