Faults - Possible causes - Solutions
8
Faults - Possible causes - Solutions
ATTENTION
In the event the burner stops, in order to prevent
any damage to the installation, do not unblock the
burner more than twice in a row. If the burner
locks out for a third time, contact the customer
service.
DANGER
In the event there are further lockouts or faults
with the burner, the maintenance interventions
must only be carried out by qualified, authorised
personnel, in accordance with the contents of this
manual and in compliance with the standards and
regulations of current laws.
Signal
Problem
Probable cause
Suggested remedy
2 blinks
Once the pre-purging
phase and safety time
have passed, the
burner goes into lockout
without the appearance
of the flame.
The operation solenoid valve lets little gas through. Increase
One of the two solenoid valves does not open
Replace
Gas pressure too low
Increase pressure at governor
Ignition electrode incorrectly adjusted
Adjust it
Electrode grounded due to broken insulation
Replace
High voltage cable defective
Replace
High voltage cable deformed by high temperature Replace and protect
Ignition transformer defective
Replace
Incorrect valve or transformer electrical wiring
Check
Defective control box
Replace
A closed valve upstream the gas train
Open
Air in pipework
Bleed air
Gas valves unconnected or with interrupted coil
Check connections or replace coil
3 blink
The burner does not
switch on, and the
lockout appears
Air pressure switch in operating position
Adjust or replace
The burner starts and
then goes into lockout
Air pressure switch does not switch owing to lack of air pressure:
Air pressure switch poorly adjusted
Adjust or replace
Pressure switch pressure point pipe clogged
Clean
Poorly adjusted head
Adjust
High pressure in the furnace
Connect air pressure switch to fan
suction line
Lockout during pre-
purging phase
Defective motor control contactor
(only three-phase version)
Replace
Defective electrical motor
Replace
Motor lockout (only three-phase version)
Replace
4 blinks
The burner starts and
then goes into lockout
Flame simulation
Replace the control box
Lockout when burner
stops
Permanent flame in the combustion head or flame
simulation
Eliminate persistence of flame or
replace control box
6 blinks
The burner starts and
then goes into lockout
Defective or incorrectly adjusted servomotor
Adjust or replace
7 blinks
The burner goes into
lockout immediately
following the
appearance of the
flame
The operation solenoid lets little gas through
Increase
Ionisation probe incorrectly adjusted
Adjust
Insufficient ionisation (less than 5 A)
Check probe position
Earth probe
Withdraw or replace cable
Burner poorly earthed
Check earthing
Phase and neutral connections inverted
Invert them
Defective flame detection circuit
Replace the control box
Burner locks out when
shifting from minimum
to maximum output and
vice versa
Too much air or too little gas
Adjust air and gas
Burner goes into
lockout during operation
Probe or ionisation cable grounded
Replace worn parts