9
20040563
GB
Technical description of the burner
4.5
Electrical data
Motor IE1
Motor IE2
Tab. C
4.6
Burner weight
The weight of the burner complete with its packaging is shown in
Tab. D.
Tab. D
Model
RS 55/E BLU
Electrical supply
V
Hz
230 - 400 with neutral ~+/-10%
50 three-phase
Fan motor
rpm
V
kW
A
2810
230 / 400
1.1
4.7 - 2.7
Ignition transformer
V1 - V2
I1 - I2
220-240 V - 1 x 15 kV
1 A - 25 mA
Absorbed electrical power
kW max
1.5
Protection level
IP40
Model
RS 55/E BLU
Electrical supply
V
Hz
230 - 400 with neutral ~+/-10%
50 three-phase
Fan motor
rpm
V
kW
A
2850
230 / 400
1.1
4 - 2.3
Ignition transformer
V1 - V2
I1 - I2
220-240 V - 1 x 15 kV
1 A - 25 mA
Absorbed electrical power
kW max
1.5
Protection level
IP40
Model
Combustion head
kg
RS 55/E BLU
TC
42
RS 55/E BLU
TL
44