20151674
42
GB
List of parameters PME71.901...)
257
Post-ignition time -0.3 seconds
Modification
0s
13.23 s
0.147 s
2.205 s
SO
OEM
400
Ratio control (operation)
403.00
Fan speed: Ignition load speed (P0)
Modification
800 rpm
900 rpm
10 rpm
3000 rpm
SO
SO
403.01
Fan speed: Low flame speed (P1)
Modification
800 rpm
900 rpm
10 rpm
1200 rpm
SO
SO
403.02
Fan speed: High flame speed (P2)
Modification
800 rpm
900 rpm
10 rpm
5700 rpm
SO
SO
500
Ratio control
503.00
Speed without PWM fan flame: Standby speed
Modification
0 rpm
9000 rpm
10 rpm
0 rpm
SO
SO
503.01
Speed without PWM fan flame: Speed of impu-
rity purge
Modification
800 rpm
9000 rpm
10 rpm
5700 rpm
SO
SO
516.00
Limit of ignition load speed (P0): Minimum limit
Modification
800 rpm
9000 rpm
10 rpm
800 rpm
SO
OEM
516.01
Limit of ignition load speed (P0): Maximum limit Modification
800 rpm
9000 rpm
10 rpm
9000 rpm
SO
OEM
517.00
Limit of low flame speed P1: Minimum limit Mod-
ification
Modification
800 rpm
9000 rpm
10 rpm
800 rpm
SO
OEM
517.01
Limit of low flame speed P1: Maximum limit
Modification
800 rpm
9000 rpm
10 rpm
9000 rpm
SO
OEM
518.00
Limit of high flame speed P2: Minimum limit
Modification
800 rpm
9000 rpm
10 rpm
800 rpm
SO
OEM
518.01
Limit of high flame speed P2: Maximum limit
Modification
800 rpm
9000 rpm
10 rpm
9000 rpm
SO
OEM
519
Maximum fan speed
Modification
3000 rpm
9000 rpm
10 rpm
5830 rpm
SO
OEM
522
low flame acceleration ® high flame
Modification
2.058 s
74.970 s
0.294 s
14.994 s
SO
OEM
523
High flame acceleration ® low flame
Modification
2.058 s
74.970 s
0.294 s
14.994 s
SO
OEM
558
Mode: Information UDS status
0 = PC tool mode
1 = PWM mode
2 = actuator mode
3 = internally
4 = internally
5 = internally
Reading only
0
5
1
0
SO
---
559
PWM mode
0 = open loop control
1 = PID control
2 = safety mode (PWM limits)
Modification
0
2
1
1
SO
OEM
560
Mode: Control of pneumatic ratio
0 = OFF
1 = PWM fan
2 = air damper actuator
Reading only
0
2
1
1
SO
---
600
Output setting
644
Number of pulses for rotation
Modification
2
5
1
3
SO
OEM
646
Time of speed control adjustment
Modification
1.029 s
2.058 s
0.147 s
2.058 s
SO
OEM
650.00
Speed tolerance range: Stopping speed
Modification
1%
5%
1%
1%
SO
OEM
650.01
Speed tolerance range: Rapid stopping speed
Modification
1%
10%
1%
3%
SO
OEM
654
Analogue input (feedback potentiometer
ASZxx.3x required)
0 = input passage 3 positions
1 = 0...10 V
2 = 0...135 W
3 = 0...20 mA
4 = 4...20 mA with lockout at I <4 mA
5 = 4...20 mA
Modification
0
5
1
1
SO
SO
658.00
PWM fan values: PWM starting
Modification
1%
100%
1%
25%
SO
OEM
658.01
PWM values fan: Min. PWM operating range
Modification
0%
20%
1%
0%
SO
OEM
658.02
PWM values fan: Max. PWM operating range
Modification
80%
100%
1%
100%
SO
OEM
659.00
Ramp time of fan: Min. low-fire to high-fire
Reading only
0s
74.970 s
0.294 s
2.058 s
SO
---
659.01
Ramp time of fan: Max. from high flame to low
flame
Reading only
0s
74.970 s
0.294 s
74.970 s
SO
---
659.02
Ramp time of fan: Min. high-fire to low-fire
Reading only
0s
74.970 s
0.294 s
2.058 s
SO
---
659.03
Ramp time of fan: Max. high-fire to low-fire
Reading only
0s
74.970 s
0.294 s
74.970 s
SO
---
660
Tolerance time speed deviation
Reading only
0s
37.85 s
0.147 s
4.998 s
SO
---
674
Neutral interval (control offset permitted)
Modification
0 rpm
255 rpm
1 rpm
40 rpm
SO
OEM
Parameter
Modification
Value range
Resolution
Factory Set-
ting
Password
reading
level to
level
Password
writing level
to level
No.
Description
Min.
Max.
Summary of Contents for RX 150 S/PV
Page 2: ...Translation of the original instructions...
Page 48: ...20151674 46 GB Appendix Electrical panel layout 0 1 0 0 1 0 RX 150 S PV...
Page 49: ...47 20151674 GB Appendix Electrical panel layout...
Page 50: ...20151674 48 GB Appendix Electrical panel layout...
Page 51: ...49 20151674 GB Appendix Electrical panel layout 0 0 0 1 1...
Page 54: ......
Page 55: ......