Start-up, calibration and operation of the burner
5.7
Flame signal measurement
Check the flame signal through the parameter 954, as indicated in
Fig. 39. The displayed value is expressed in percentage.
The value during the operation must be higher than 24%. If at the
burner start-up the value is higher or equal of 18%, the burner locks
out due to the extraneous light.
For further and specific information, please refer to the specific in-
struction manual. The display (Fig. 39) shows parameter
954
:
flashing on the left.
On the right, the flame’s intensity is displayed as a percentage.
Example:
954: 0.0
5.8
Final checks (with the burner working)
Tab. L
S8171
P
V
h
min s
%
Fig. 39
Open the control limit operation
Open the high limit operation
The burner must stop
Rotate the maximum gas pressure switch knob to the mini-
mum end-of-scale position
Rotate the air pressure switch knob to the maximum end of
scale position
The burner must stop in lockout
Switch off the burner and disconnect the voltage
Disconnect the minimum gas pressure switch
The burner must not start
Cover the flame sensor
The burner must stop in lockout due to firing failure
WARNING
Make sure that the mechanical locking systems on
the different adjustment devices are fully tightened.