background image

 

User & Operations Manual 
Sentinel DUAL UL 
True-Online UPS System 

 

1000 VA -1500 VA - 2000 VA - 3000 VA 

 
 
 
 
 

Summary of Contents for SDH 1000 UL

Page 1: ...User Operations Manual Sentinel DUAL UL True Online UPS System 1000 VA 1500 VA 2000 VA 3000 VA...

Page 2: ...environmental aspects All our products pursue the objectives defined in the environmental management system developed by the company in compliance with applicable standards No hazardous materials such...

Page 3: ...ON 12 TOWER VERSION WITH BATTERY BOX 13 RACK VERSION 14 USE 15 CONNECTIONS AND SWITCHING ON FOR THE FIRST TIME 15 SWITCHING ON FROM THE MAINS 15 SWITCHING ON FROM THE BATTERY 15 SWITCHING OFF THE UPS...

Page 4: ...4 COMMUNICATION SLOT 25 BATTERY PACK REPLACEMENT 26 TROUBLESHOOTING 28 ALARM CODES 30 FAULT 30 LOCK 31 TECHNICAL DATA 32...

Page 5: ...an be installed in the two different positions The UPS is also equipped with a dedicated battery pack that allows for easy battery replacement hot swap in complete safety thanks to the protected conne...

Page 6: ...6 UPS VIEWS FRONT VIEW Extractable rotatable display plate Removable front panel Release slits Battery pack connector ON OFF Switch Battery pack retention panel...

Page 7: ...A Communication port RS232 Battery expansion connector optional USB communication port NEMA 10A output socket NEMA 16A output socket NEMA 16A input plug Communication Card Slots NEMA 10A input plug Co...

Page 8: ...ad level indicator ON button Configuration area STAND BY button Maintenance request Regular operation Timer Mains operation Measurement display area Battery operation Stand by alarm Load powered by by...

Page 9: ...number of batteries contained can vary according to the type of UPS for which the BATTERY BOX is intended It is therefore necessary to take great care to ensure that the battery voltage of the BATTER...

Page 10: ...CK After opening the packaging it is first necessary to check the contents The package must contain UPS Support feet USB cable RS232 cable User manual CD Safety manual Handles for rack installation Ha...

Page 11: ...interference in which case the user may be required to take additional measures BATTERY BOX INSTALLATION ATTENTION CHECK ON THE DATA PLATE THAT THE VOLTAGE OF THE BATTERY BOX IS THE SAME AS THAT ALLOW...

Page 12: ...SURE THAT THE UPS IS COMPLETELY SWITCHED OFF AND NOT CONNECTED TO THE MAINS POWER SUPPLY OR TO ANY LOAD Once removed from the packaging the UPS is already preset for installation in the tower configu...

Page 13: ...AD THE BATTERY BOX IS DISCONNECTED FROM THE UPS FROM ANY OTHER BATTERY BOXES AND WITH THE BATTERY ISOLATOR OPEN For the battery box version each foot is composed of three parts two supports and an ext...

Page 14: ...gently pull it away from its position just enough to be able to rotate it ATTENTION The panel must be removed carefully DO NOT ATTEMPT IN ANY WAY TO REMOVE THE PANEL FROM THE UPS 2 Rotate the panel 9...

Page 15: ...download_categories SWITCHING ON FROM THE MAINS 1 Press the ON button for 1 second After pressing it all the icons on the display light up for 1 second and the UPS beeps 2 Switch on the equipment con...

Page 16: ...ntervals Flashing Low battery pre alarm Indicates that battery autonomy is coming to an end In this condition the UPS emits a beep at regular 1 second intervals Fixed Indicates that the loads connecte...

Page 17: ...xamples are shown below GRAPHIC EXAMPLE 1 DESCRIPTION GRAPHIC EXAMPLE 1 DESCRIPTION Mains voltage Total battery voltage Mains frequency Applied load percentage UPS output voltage Current absorbed by t...

Page 18: ...ters press the ON button for UP or press the SEL button for down To confirm the parameters chosen hold down the STBY button for at least 200 milliseconds To return to upper menu if it is not in top me...

Page 19: ...Setting Parameter 2 Enable or disable Bypass function You may choose the following two options ENA Bypass enable DIS Bypass disable Default 06 Programmable outlets enable disable Interface Setting Par...

Page 20: ...end on battery capacity Default Note When setting as 0 the backup time will be only 10 seconds 09 Battery total AH setting Interface Setting Parameter 2 Set up the battery total AH of the UPS 7 999 se...

Page 21: ...rtain period of battery operation or when the pre alarm threshold for battery discharge has been reached or when an overloading event occurs By default the Energyshare sockets are not configured and t...

Page 22: ...ll display of the status of the UPS via USB or RS232 For a list of possible configurations available to the user refer to the UPS Configuration paragraph INSTALLATION OPERATIONS 1 Connect one of the U...

Page 23: ...d Disabled Bypass when UPS is off Bypass when UPS is off enable or disable Disabled Enabled Disabled Programmable outlets Programmable outlets control enable or disable when the UPS work on battery mo...

Page 24: ...protection enable or disable Enabled Enabled Disabled Site fault detection Site fault detection enable or disable Enabled Enabled Disabled Bypass voltage thresholds Selects the permitted voltage rang...

Page 25: ...rfacing with the UPS refer to the manual provided 3 RXD 5 GND COMMUNICATION SLOT The UPS is equipped with an expansion slot for optional communication cards see figure on right which allows the device...

Page 26: ...ACK IS VERY HEAVY USE EXTREME CAUTION WHEN REPLACING IT 1 Set the UPS to bypass mode manually by pressing the ON SEL buttons for 4 seconds see paragraph entitled USE Configuration of Operating Mode Th...

Page 27: ...tteries see the label located on the battery pack near the connector 5 Insert the new battery pack into the compartment sliding it into the UPS Put the battery pack retention panel back in position an...

Page 28: ...upply mode in fact only powers the loads in the event of a blackout NO CONNECTION TO THE LOAD Check the connection to the load THE UPS IS OPERATING FROM THE BATTERY DESPITE THE PRESENCE OF MAINS VOLTA...

Page 29: ...nd back on again reconnect the utilities one at a time to identify which one is faulty THE BUZZER SOUNDS CONTINUOUSLY AND THE DISPLAY SHOWS ONE OF THE FOLLOWING CODES F60 L03 L13 L20 L21 L40 L41 L42 L...

Page 30: ...blems which do not cause the lock of the UPS but reduce performance or prevent certain functions from being used CODE DESCRIPTION A61 Replace batteries A62 Batteries missing or Battery Box missing or...

Page 31: ...f of the inverter and the load being powered by the bypass line this procedure is excluded for locks due to serious persistent overloads and short circuits CODE DESCRIPTION L03 Incorrect auxiliary pow...

Page 32: ...ass line not available locks after 5 Line mode 2 Battery mode minutes Overload 130 load 140 Bypass line available activates the bypass after 30 10 seconds locks after 1 minute Bypass line not availabl...

Page 33: ...040W 100Vac input SDH 2000 UL 110 127Vac 50 60Hz 16A 1 100 110 115 120 125 127Vac 50 60Hz 1 2000VA 1930W 127Vac input 2000VA 1930W 125Vac input 2000VA 1850W 120Vac input 2000VA 1740W 115Vac input 2000...

Page 34: ...0MLSDH1K0RUENUD...

Reviews: