18
C
ONFIGURING THE
UPS
PARAMETERS
The area of the display shown in the figure displays the setting interface
and allows the user to configure some UPS parameters directly from the
display panel.
HOW TO PROCEED:
To enter the setting mode, hold down the “SEL” button for at least 3 seconds when the UPS is in STANDBY-BY
mode.
The setting item 1 will be show.
To change the different setting item, press the “ON” button for UP, or press the “SEL” button for down.
To confirm the setting item chosen, hold down the “STBY” button for at least 200 milliseconds.
After enter setting item chosen, to change the different parameters, press the “ON” button for UP, or press the
“SEL” button for down.
To confirm the parameters chosen, hold down the “STBY” button for at least 200 milliseconds.
To return to upper menu if it is not in top menu or exit the setting mode if it is in top menu, hold down the “ON”
and “SEL” button for at least 200 milliseconds.
P
OSSIBLE SETTINGS
01: Output voltage setting
Interface Setting
Parameter 2: Output voltage
100:
presents output voltage is 100Vac
110:
presents output voltage is 110Vac
115:
presents output voltage is 115Vac
120:
presents output voltage is 120Vac (Default)
127:
presents output voltage is 127Vac
02: Frequency Converter enable/disable
Interface Setting
Parameter 2:
Enable or disable converter mode. You may choose the
following two options:
ENA:
converter mode enable
DIS:
converter mode disable (Default)