19
03: Output frequency setting
Interface Setting
Parameter 2: Output frequency setting.
50:
presents output frequency is 50Hz
60:
presents output frequency is 60Hz
04: ECO enable/disable
Interface Setting
Parameter 2:
Enable or disable ECO function. You may choose the
following two options:
ENA:
ECO mode enable
DIS:
ECO mode disable (Default)
05: Bypass enable/disable when UPS is off
Interface Setting
Parameter 2:
Enable or disable Bypass function. You may choose the
following two options:
ENA:
Bypass enable
DIS:
Bypass disable (Default)
06: Programmable outlets enable/disable
Interface Setting
Parameter 2:
Enable or disable programmable outlets.
ENA:
Programmable outlets enable
DIS:
Programmable outlets disable (Default)
07: Programmable outlets setting
Interface Setting
Parameter 2:
Set up backup time limits for programmable outlets.
0-999:
setting the backup time limits in minutes from 0-999 for
programmable outlets which connect to non-critical devices on battery
mode. (Default: 999)