MANUAL BYPASS
Using the Manual Bypass feature, the UPS can be switched to bypass. In this condition the load is powered directly by
the input mains, any disruption in the mains directly affects the load.
CAUTION:
BEFORE CARRYING OUT THE FOLLOWING SEQUENCE OF OPERATIONS, ENSURE THAT THE UPS’S
INPUT AND OUTPUT FREQUENCY COINCIDE AND THAT THE UPS IS NOT OPERATING FROM THE
BATTERY
Attention: even when the UPS is switched on, the load is disconnected in the event of a mains blackout.
If the input mains deviates from the established tolerances, the UPS automatically switches to Stdby mode and
disconnects the load.
To force the UPS into manual bypass mode, press and hold down the ON and SEL keys simultaneously for at least 4
seconds.
The code "C02" appears on the display.
To return to the normal operation mode press the ON and SEL keys again for at least 4 sec.
PROGRAMMABLE AUXILIARY SOCKET (EnergyShare)
The EnergyShare sockets are outlets that allow for the automatic disconnection of the load applied to them in certain
operating conditions. The events that determine automatic disconnection of the EnergyShare sockets can be selected by
the user through the
UPStools
configuration software. For example, it is possible to select disconnection after a certain
period of battery operation; or when the pre-alarm threshold for battery discharge has been reached, or when an
overloading event occurs.
By default the Energyshare sockets are not configured and therefore function as other outlets.
The EnergyShare function is associated with an icon on the display whose meaning is explained in the paragraph
entitled “
Display panel indications
”
The presence and the number of these sockets depend on the UPS type, and they are distinguished by a different color
with respect to other sockets.
REMOTE CONTROL TERMINAL BOARD
The remote control terminal allows for implementation of the REPO function (Remote Emergency Power Off).
The UPS is provided by the manufacturer with the REPO terminals short-circuited. For installation remove the short
circuit and connect to the device's normally closed contact
In case of an emergency, if the stop device is used, the REPO control is opened and the UPS goes into stand-by mode
and the load is completely disconnected.
Attention:
before restarting the UPS, reset the stop device.
The circuitry of the remote control terminal board is self-powered with SELV circuits. Therefore, an external voltage
supply is not required. When a contact is closed, a maximum current of 15mA circulates.
All connections with the remote control terminal board are made through a cable which guarantees a double insulation
connection.
Logic of the connections:
PIN 1-2 REPO
The function is activated when the contact is opened.