24
FUNCTION
DESCRIPTION
DEFAULT
POSSIBLE CONFIGURATIONS
Alarm at battery
mode
Alarm at battery mode
enable or disable
Enabled
Enabled
Disabled
Auto reboot
Auto reboot enable or
disable
Enabled
Enabled
Disabled
Green power
function
Green power function
enable or disable
Disabled
Enabled
Disabled
Cold start
Cold start enable or disable
Enabled
Enabled
Disabled
Bypass not
allowed
Bypass not allowed enable
or disable
Disabled
Enabled
Disabled
Battery deep-
discharging
protection
Battery deep-discharging
protection enable or disable
Enabled
Enabled
Disabled
Site fault
detection
Site fault detection enable
or disable
Enabled
Enabled
Disabled
Bypass voltage
thresholds
Selects the permitted
voltage range for switching
to the bypass
Low: 85V
High: 132V
Low: 180 - 200 in 1V steps
High: 85 - 115 in 1V steps
Input frequency
tolerance range
Selects the permitted range
for the input frequency for
switching to the bypass and
for the synchronisation of
the output
± 3Hz
(±1 - ±5) in 0.1 Hz steps
Bypass voltage
threshold for ECO
Selects the permitted
voltage range for operation
in ECO mode
Low:
-6V
High: +6V
Low: -(3 – 12) in 1V steps
High: +(3 – 12) in 1V steps
Battery numbers
in parallels
Selects battery group
numbers
0
0 – 99 in 1 steps