31
Active commands:
Indicates the presence of an active remote command.
CODE
DESCRIPTION
C01
Emergency power off
C02
load on bypass or manual bypass command
C04
Battery test in progress
L
OCK
LOCK alerts are normally preceded by an alarm signal and their scale leads to the power-off of the inverter and the load
being powered by the bypass line (this procedure is excluded for locks due to serious, persistent overloads and short
circuits).
CODE
DESCRIPTION
L03
Incorrect auxiliary power supply
L04
Over temperature
L13
Capacitor pre-charge failed
L20
Capacitor bank undervoltage
L21
Capacitor bank overvoltage
L40
Inverter overvoltage
L41
Continuous output voltage
L43
Inverter undervoltage
L50
Overload
L53
Short circuit
L66
Over input current
L67
Battery fault