TECHNICAL DATA
UPS MODELS
SDH 1000 UL
SDH 1500 UL
SDH 2000 UL SDH 3000 UL
INPUT
Nominal voltage
[Vac]
100 / 110 / 115 / 120 / 127
Maximum operating voltage
[Vac]
150
Nominal frequency
[Hz]
50/60
Rated current (1)
[A]
13.2
13.2
17.6
26.4
BATTERY
Recharge time (only internal battery) [h]
< 4h for 80% of the load
No. of internal batteries
3
3
6 / 0
6 / 0
Expandability and nominal voltage of the
Battery Box
36Vdc 36Vdc 72Vdc 72Vdc
Charging
current(Max)
8A 8A 8A 8A
OUTPUT
Nominal voltage (2)
[Vac]
Selectable: 100 / 110 / 115 / 120 / 127
Frequency (3)
[Hz]
Selectable: 50, 60 or
auto sensing
Nominal
power(5)
[VA]
1000 1500 2000 3000
Nominal
power(5)
[W]
1000 1500 2000 3000
Overload: 100% < load < 110%
Overload warning only
Overload: 110% < load < 130%
Bypass line available:
activates the bypass after
5(Line mode) /2(Battery mode)
minutes, locks after 30
(110%~120%) /10
(120%~130%) minutes.
Bypass line not available:
locks after 5(Line mode)
/2(Battery mode) minutes
Overload: 130% < load < 140%
Bypass line available:
activates the bypass after
30/10 seconds, locks after 1
minute.
Bypass line not available:
locks after 10 seconds
Overload load > 140%
Bypass line available:
activates the bypass after 1.5
seconds, locks after 1 minute.
Bypass line not available:
locks after 1.5 seconds
OTHER DATA
Leakage current towards ground
[mA]
< 1,0
Room temperature (4)
[°C/°F]
0 – 40 / 32 - 104
Humidity
< 90% without condensation
Protection devices
excessive battery discharge - over current - short circuit - over
voltage - under voltage - thermal
Dimensions W x D x H (5)
[in]
3.42 x 16.73 x 17.71
3.42 x 24.60 x 17.71
Dimensions W x D x H (5)
[mm]
87 x 425 x 450
87 x 625 x 450
Weight [Lb]
37.48
39.68 58.42 68.34
Weight [kg]
17
18
26.5
31
For additional details regarding technical data refer to website
(1)
Input power cord safety specification