33
(3)
If the network frequency is within ± 3Hz of the selected value, the UPS is synchronized with the network. If the frequency is out of
tolerance range or in battery operation, the frequency is that se0.1%
(4)
20 - 25 °C / 68 – 77 °F for longer battery life
(5)
Output Power Rating Table
Model name
Input rating
Output rating
SDH 1000 UL
110-127Vac, 50/60Hz,
12A, 1Ø
100/110/115/120/125/127Vac, 50/60Hz,
1000VA/1000W, 1Ø, 10A
SDH 1500 UL
110-127Vac, 50/60Hz,
12A, 1Ø
100/110/115/120/125/127Vac, 50/60Hz, 1Ø
1500VA/1450W (@127Vac input) ;
1500VA/1430W (@125Vac input) ;
1500VA/1300W (@120Vac input) ;
1500VA/1270W (@115Vac input) ;
1500VA/1200W (@110Vac input) ;
1500VA/1040W (@100Vac input)
SDH 2000 UL
110-127Vac, 50/60Hz,
16A, 1Ø
100/110/115/120/125/127Vac, 50/60Hz, 1Ø
2000VA/1930W (@127Vac input) ;
2000VA/1930W (@125Vac input) ;
2000VA/1850W (@120Vac input) ;
2000VA/1740W (@115Vac input) ;
2000VA/1640W (@110Vac input) ;
2000VA/1500W (@100Vac input)
SDH 3000 UL
110-127Vac, 50/60Hz,
24A, 1Ø
100/110/115/120/125/127Vac, 50/60Hz, 1Ø
3000VA/2880W (@127Vac input) ;
3000VA/2850W (@125Vac input) ;
3000VA/2740W (@120Vac input) ;
3000VA/2650W (@115Vac input) ;
3000VA/2500W (@110Vac input) ;
3000VA/2300W (@100Vac input)
BATTERY BOX MODELS
JSDH036-NPA- JSDH036-NPM- JSDH072-NPA- JSDH072-NPM-
Battery rated voltage
[Vdc]
36Vdc
72Vdc
Dimensions W x D x H
[in]
3.42 x 16.73 x 17.71
3.42 x 24.60 x 17.71
Dimensions W x D x H
[mm]
87 x 425 x 450
87 x 625 x 450
Weight [Lb]
29.76
45.19 55.11 83.77
Weight [kg]
13.5
20.5
25
38
The "-" symbol replaces an alphanumeric code for internal use