24
TECHNICAL DATA
UPS MODELS
SEP 700
SEP 1000
SEP 1000 ER
SEP 1500
SEP 2200
SEP 2200 ER
SEP 3000
SEP 3000 ER
INPUT
Nominal voltage
[Vac]
220 - 230 - 240
Maximum operating voltage
[Vac]
300
Nominal frequency
[Hz]
50 - 60
Nominal current (1)
[A]
3.3
4.5
6.5
9.5
12.5
BATTERY
Recharge time (standard versions)
[h]
< 4h for 80% of the load
Expandability and nominal
voltage of the Battery Box
Not
expandable
36Vdc
Not
expandable
72Vdc 72Vdc
Charging current
(for ER versions only)
Not
applicable
8A
Not
applicable
8A 8A
OUTPUT
Nominal voltage (4)
[Vac]
Selectable: 220 /
230
/ 240
Frequency (2)
[Hz]
Selectable: 50, 60 or
auto sensing
Nominal power
[VA]
700VA
1000VA
1500VA
2200VA
3000VA
Nominal power
[W]
560W
800W
1200W
1760W
2400W
Overload: 100% < load < 110%
Bypass line available:
activates the bypass after 2 seconds
locks
after
120
seconds
Bypass line not available:
locks after 60 seconds
Overload: 110% < load < 150%
Bypass line available:
activates the bypass after 2 seconds
locks after 4 seconds
Bypass line not available:
locks after 4 seconds
Overload load > 150%
Bypass line available:
activates the bypass instantly
locks after 1 second
Bypass line not available:
locks after 0.5 seconds
OTHER
Leakage current to earth
[mA]
< 1,5mA
< 2mA
Ambient temperature (3)
[°C]
0 – 40
Humidity
< 90% without condensation
Protection devices
excessively low batteries - overcurrent - short circuit - overvoltage -
undervoltage - circuit breaker
Dimensions W x D x H
[mm]
158 x 422 x 235
190 x 446 x 333
Weight [kg]
11
13
14
26
28
Weight (for ER versions only)
[kg]
Not
applicable
7
Not
applicable
14 15
For more details please consult the web site
(1)
at nominal load, nominal voltage of 230 Vac, battery charging
(2)
If the mains frequency is within ±5% of the selected value, the UPS is synchronised with the mains. If the frequency is
out of the tolerance range or operating from the battery, the frequency is the one selected ±0.1%
(3)
20 - 25 °C for longer battery life
(4)
To keep the output voltage within the indicated range of precision, recalibration may be necessary after a long period
of operation