W

IRING THE 

UPS 

The Socle Box is equipped with different openings on its various sides and an inner holed bar to simplify 
the wiring operations of the UPS. 
 

 

 

 

A

 –

  Upper 

fixed opening

 for the passage of wires coming from the UPS. 

B

 –

 

Recloseable  windows

  on  both  sides.  Designed  to  facilitate  working  inside  the  Socle  Box  and  to 

allow the passage of wires from the rear part if necessary. 

C

 –

 

Mobile  lower  window

  for  the  passage  of  wires,  equipped  with  adjustable  closure,  depending  on 

needs. 

D

 –

 

Holed bar

 to allow tightening the wires which pass through the Socle Box using simple clamps. The 

bar can be raised/lowered using the dedicated fastening holes on the sides, as shown in figure (see 

d1

). Each of these holes can be used for grounding the Socle Box using a screw present on one of 

the side bars (see 

d1

). 

 

F

INAL ASSEMBLY

 

Once the UPS wiring is complete and any windows not used by the Socle Box have been closed, proceed 
with  securing  the  UPS  using  the  2  side  fixing  brackets  and  the  8  galvanised  M6x8  screws  supplied. 
Assemble the front bulkhead using the 8 black M4x8 screws supplied. 
The structure thus obtained is stable as a whole and post-installation handling operations can be carried 
out  safely;  but  if  environmental  circumstances  or  supply  requirements  require  the  ups  be  fixed  to  the 
ground, use the two L-shaped brackets supplied with the Socle Box to secure it to the ground. 
 

 

 

 

 