3 .6
Calibrating combustion parameters
TAU 35 UNIT
boilers are calibrated in the factory for G20/
G25 20/25 mbar.
If actual combustion parameter values differ from those
given in the tables below, contact
R
’s Technical As-
sistance Service.
Proceed as follows to set combustion parameters:
− Press and hold the
T
and
R
keys for betwe-
en 3 and 6 seconds to enter chimney sweep
mode. The ‘chimney sweep’ symbol on the di-
splay starts to flash and the display reads out the
current boiler temperature.
− To set combustion parameters for maximum and
minimum power, press and hold the
T
and
R
keys simultaneously for over 6 seconds. The
boiler enters fan speed control mode
− Press the
U
key.
The fan switches to maximum speed.
− Insert the combustion analysis probe into the
socket (1) in the flue gas vent fitting.
− Set the CO
2
level by turning the adjuster screw (2)
on the fan group. Turn the screw clockwise to re-
duce CO
2
, anti-clockwise to increase CO
2
.
Once the adjustments are complete, the
combustion parameters should be as specified
in the tables below.
2
1
CO
2
values for functioning at MAXIMUM POWER
TAU 35 UNIT
G20
9,15
G31
10,2