52
TECHNICAL ASSISTANCE SERVICE
Error
code
via QAA
Diagnostic
info
Description of error
Type of fault
System action
Procedure
0
0
No input code
No input code
-
-
0
473
No input code
No input code
Message
-
10
150
Outdoor temperature
sensor error
Short circuit in outdoor
temperature sensor
Message
Check/replace outdoor
temperature sensor
10
151
Outdoor temperature
sensor error
Outdoor temperature sen-
sor faulty
Message
Check/replace outdoor
temperature sensor
20
142
Boiler sensor 1 error
Short circuit in tempera-
ture sensor B2
Safety shutdown
Check/replace tempera-
ture sensor
20
143
Boiler sensor 1 error
Temperature sensor B2
faulty
Safety shutdown
Check/replace tempera-
ture sensor
20
405
Boiler sensor 1 error
Boiler sensor 1 error
Safety shutdown
Check/replace tempera-
ture sensor
20
406
Boiler sensor 1 error
Boiler sensor 1 error
Safety shutdown
Check/replace tempera-
ture sensor
20
410
Boiler sensor 1 error
Short circuit in tempera-
ture sensor B2
Burner lockout
(permanent).
Lockout reset re-
quired
Check/replace tempera-
ture sensor
20
411
Boiler sensor 1 error
Temperature sensor B2
faulty
Burner lockout
(permanent).
Lockout reset re-
quired
Check/replace tempera-
ture sensor
20
412
Boiler sensor 1 error
No further differentiation
Burner lockout
(permanent).
Lockout reset re-
quired
Check/replace tempera-
ture sensor
20
413
Boiler sensor 1 error
No further differentiation
Burner lockout
(permanent).
Lockout reset re-
quired
Check/replace tempera-
ture sensor
28
152
Flue gas sensor error
Short circuit in tempera-
ture sensor
Message
Check/replace flue gas
temperature sensor
28
153
Flue gas sensor error Temperature sensor faulty
Message
Check/replace flue gas
temperature sensor
28
507
Flue gas sensor error
Temperature reading not
plausible
Safety shutdown
Check/replace flue gas
temperature sensor
32
524
CH flow sensor 2 error Short circuit in CH 2 tem-
perature sensor
Message
Check/replace tempera-
ture sensor
32
525
CH flow sensor 2 error
CH 2 temperature sensor
faulty
Message
Check/replace tempera-
ture sensor
32
546
CH flow sensor 2 error
Short circuit in additional
zone clip-in temperature
sensor (accessory)
Message
Check/replace tempera-
ture sensor
32
547
CH flow sensor 2 error
Additional zone clip-in
temperature sensor faulty
(accessory)
Message
Check/replace tempera-
ture sensor
40
144
CH return sensor 1
error
Short circuit in return
temperature sensor (B7)
Safety shutdown
Check/replace tempera-
ture sensor
40
145
CH return sensor 1
error
Return temperature sen-
sor (B7) faulty
Safety shutdown
Check/replace tempera-
ture sensor
40
407
CH return sensor 1
error
No further differentiation
Safety shutdown
Check/replace tempera-
ture sensor
40
408
CH return sensor 1
error
No further differentiation
Safety shutdown
Check/replace tempera-
ture sensor
40
414
CH return sensor 1
error
Short circuit in return
temperature sensor (B7)
Burner lockout
(permanent).
Lockout reset re-
quired
Check/replace tempera-
ture sensor
ERROR TABLE