71
TECHNICAL ASSISTANCE SERVICE
3 .11
Maintenance
3 .12
Removing the burner
Regular maintenance is a legal requirement. It is also
essential for the safety, efficiency and durability of the
boiler. Proper maintenance keeps consumption and
emissions down, and ensures that the boiler continues
to operate reliably over time.
Perform the following operations before beginning any
maintenance:
− Switch the electricity supply OFF at the system’s
main switch and at the control panel
− Close the fuel shut-off cocks.
9
On completion of maintenance, the original settings
must be restored and combustion fumes analysed
to verify correct functioning.
Proceed as follows to remove the burner:
− Remove the front panel and the top panel from
the boiler.
− Unscrew the nut (1) securing the gas feed pipe to
the gas valve (2).
− Loosen the hose clamp (3) and remove the air in-
take pipe (4).
− Pull the hose (5) off the pressure measurement
union on gas valve (2).
− Disconnect the cable (6) from the ignition elec-
trode.
− Unscrew the screws (7) and remove the ignition
transformer (8).
− Remove the three nuts (9) securing the burner to
the flue gas box. Remove the burner, taking care
not to damage the seal (10).
Reverse the above steps to fit the burner again.
2
9
6
8
5
1
9
3
7
4
10