74
TECHNICAL ASSISTANCE SERVICE
FAULT
CAUSE
SOLUTION
There is a smell of gas
Leaks from the supply circuit
− Check that all joints are tight and that
the pressure measurement points are
closed
There is a smell of fumes
Fumes escaping into the air
− Check that the boiler body is clean
− Check that the flue pipes are clean
− Check the condition of the boiler seals
− Check the quality of combustion
The boiler reaches the set tem-
perature but the radiators are still
cold
Air in the circuit
− Bleed the circuit
Pump malfunctioning
− Unseize the pump
− Change the pump
The boiler does not reach its tem-
perature setpoint
Burner dirty
− Clean the combustion chamber
Insufficient air/fuel flow to burner
− Check and adjust the burner
Incorrect boiler temperature
setpoint
− Check the temperature setting
Burner locks out
Incorrect boiler temperature
setpoint
− Check correct functioning
− Check the temperature setting
− Check electrical wiring
No water supply
− Check the vent and bleed valves
− Check CH circuit pressure