background image

 

21 

 

UPS

 CONFIGURATION

 

The table below illustrates all the possible configurations available to the user in order to best adapt the UPS for 
individual requirements. It is possible to perform these operations using the 

UPStools

 software. 

 

FUNCTION 

DESCRIPTION 

DEFAULT 

POSSIBLE CONFIGURATIONS 

 

 

Output  

frequency 

Selects the nominal output 
frequency 

Auto 

 50 Hz 

 60 Hz 

  Auto: automatic learning of the input frequency

 

 

 

 

Output voltage 

Selects the nominal output 
voltage 

230V 

220 - 240 in 1V steps 

 

 

 

 

Operating mode 

Select one of the available 
operating modes 

L.I. 

 L.I. 

 ECO 

 OTHER (MODE) 

 

 

 

 

Power-off due to 

minimum charge 

Automatic UPS power-off in 
battery operation mode if 
the charge is lower than 5% 

Disabled 

 Enabled 

 Disabled 

 

 

 

 

Autonomy limit 

Maximum battery operation 
time 

Disabled 

  Disabled (complete battery discharge) 

  (1 - 65000) sec.  in 1 sec steps 

 

 

 

 

Battery low 

warning 

Estimated autonomy time 
remaining for the battery 
low warning 

3 min. 

(1 - 255) min.  in 1 min steps 

 

 

 

 

Battery test 

Interval of time for the 
automatic battery test 

40 hours 

 Disabled 

  (1 - 1000) h in 1 hour steps 

 

 

 

 

Maximum charge 

alarm threshold 

Selects the user overcharge 
limit 

Disabled 

 Disabled 

  (0 - 103) %  in 1% steps 

 

 

EnergyShare 

Select the auxiliary socket 
operating mode 

Always 

connected 

 Always connected 

 Disconnection after no. seconds of battery 

operation 

  Disconnection after no. seconds of the battery 

discharge pre-alarm signal 

 ... (see 

UPStools

 manual) 

 

 

 

 

Input frequency 
tolerance range 

Select the required input 
frequency range for normal 
operation 

± 5% 

(±3 - ±10) %  in 1% steps 

 

 

 

 

Power-on delay 

Waiting time for automatic 
switching back on after 
mains power returns 

5 sec. 

 Disabled 

  (1 - 255) sec.  in 1 sec steps 

 

 

 

 

Remote Switch 

on/off feature 

Select the feature 
associated with the remote 
control terminal board. 

Pin 1-2 REPO 

Pin 2-3 Remote 

ON 

  Pin 1-2 REPO 

  Pin 2-3 Remote ON, Remote ON/OFF 

 

 

Summary of Contents for VSD 1100

Page 1: ......

Page 2: ...g the environmental aspects All our products pursue the objectives defined in the environmental management system developed by the company in ompliance with applicable standards c o hazardous materials such as CFCs HCFCs or asbestos are used in this product N When evaluating packaging the choice of material has been made favouring recyclable materials For correct disposal please separate and ident...

Page 3: ...R VERSION WITH BATTERY BOX 13 RACK VERSION 14 USE 15 CONNECTIONS AND SWITCHING ON FOR THE FIRST TIME 15 SWITCHING ON FROM THE MAINS 15 SWITCHING ON FROM THE BATTERY 15 SWITCHING OFF THE UPS 15 DISPLAY PANEL MESSAGES 16 UPS STATUS MESSAGES 16 MEASUREMENT DISPLAY AREA 17 CONFIGURING THE OPERATING MODE 18 POSSIBLE SETTINGS 18 ADDITIONAL FUNCTIONS 18 SOFTWARE 20 MONITORING AND CONTROL SOFTWARE 20 CONF...

Page 4: ...4 BATTERY PACK REPLACEMENT 23 TROUBLESHOOTING 25 ALARM CODES 27 FAULT 27 LOCK 28 TECHNICAL DATA 29 ...

Page 5: ...sturbances from the mains supply This family was designed with versatility in mind allowing for installation in both tower and rack positions The following shows how the product can be installed in the two different positions The UPS is also equipped with a dedicated battery pack that allows for easy battery replacement hot swap in complete safety thanks to the protected connection system It is po...

Page 6: ...6 UPS VIEWS FRONT VIEW Extractable rotatable display plate Removable front panel Release slits Battery pack connector ON OFF Switch Battery pack retention panel ...

Page 7: ...A Communication port RS232 Battery expansion connector optional USB communication port IEC 10A output socket IEC 16A output socket IEC 16A input plug Communication Card Slots IEC 10A input plug Cooling fans Circuit breaker Remote control terminal board ...

Page 8: ...lect Load level indicator ON button Configuration area STAND BY button Maintenance request Regular operation Timer Mains operation Measurement display area Battery operation Stand by alarm AVR active EnergyShare Battery charge indicator ...

Page 9: ... to the type of UPS for which the BATTERY BOX is intended It is therefore necessary to take great care to ensure that the battery voltage of the BATTERY BOX is the same as the voltage permitted by the UPS everal battery boxes can be connected in series to achieve a longer extended runtime S f the UPS is connected to a battery box the maximum active power is derated from PF 0 9 to PF 0 8 I REAR VIE...

Page 10: ... to check the contents T UPS Support feet Schuko power cable IEC 10A IEC 16A only for models 2200 3000VA 2 IEC 10A connection cables USB cable RS232 cable User manual CD Safety manual Handles for rack installation Handle screws Battery expansion plug ER version only IEC 16A male plug For 2200 3000VA models only ...

Page 11: ...T THE VOLTAGE OF THE BATTERY BOX IS THE SAME AS THAT ALLOWED BY THE UPS can be installed in series for extended runtimes Connect the Battery Boxes in series as shown in the the UPS is connected to a battery box the maximum active power is derated from PF 0 9 to PF 0 8 rnal batteries using the dedicated configuration software UPSTools contained he battery box must only be installed while the UPS is...

Page 12: ...E SURE THAT THE UPS IS COMPLETELY SWITCHED OFF AND NOT CONNECTED TO THE MAINS POWER SUPPLY OR TO ANY LOAD the tower configuration Once removed from the packaging the UPS is already preset for installation in o complete the configuration simply mount the UPS on the two support feet T Each leg consists of two parts connecting to each other at joints To put a leg together proceed as shown in the figu...

Page 13: ...OAD THE BATTERY BOX IS DISCONNECTED FROM THE UPS FROM ANY OTHER BATTERY BOXES AND WITH THE BATTERY ISOLATOR OPEN For the battery box version each foot is composed of three parts two supports and an extension Assemble two feet as indicated in the figure below Slide the UPS and the battery box into the two supports For any additional battery boxes repeat the sequence of operations shown above ...

Page 14: ...nd gently pull it away from its position just enough to be able to rotate it ATTENTION The panel must be removed carefully DO NOT ATTEMPT IN ANY WAY TO REMOVE THE PANEL FROM THE UPS 2 Rotate the panel 90 counter clockwise and reinsert it carefully into the special housing 3 At this point with the UPS or battery box in the horizontal position secure the handles using the screws provided as shown in...

Page 15: ...perating modes paragraph to set the required mode For advanced UPS configurations execute the software UPSTools which can be downloaded from the web site www riello ups com SWITCHING ON FROM THE MAINS 1 Press the ON button for 1 second After pressing it all the icons on the display light up for 1 second and the UPS beeps 2 Switch on the equipment connected to the UPS When switching on for the firs...

Page 16: ...s the estimated percentage charge of the batteries Dynamic Indicates the percentage of charge applied to the UPS compared with the nominal value Flashing Maintenance is required Contact the support centre Fixed Indicates that the timer is active programmed switch on and switch off The timer can be activated deactivated using the software provided Flashing 1 minute until the UPS switches back on or...

Page 17: ... examples are shown below GRAPHIC EXAMPLE 1 DESCRIPTION GRAPHIC EXAMPLE 1 DESCRIPTION Mains voltage Battery charge percentage Mains frequency Total battery voltage UPS output voltage Applied load percentage Output voltage frequency Current absorbed by the load Residual battery autonomy Temperature of the electronics cooling system inside the UPS Fault Alarm 2 the corresponding code is displayed Lo...

Page 18: ...switched on the load is disconnected in the event of a mains blackout If the input mains deviates from the established tolerances the UPS automatically switches to Stdby mode and isconnects the load d de press and hold the ON and SEL keys at the same time for at least 4 sec To force the UPS into battery swap mo The code C02 appears on the display o return to the normal operation mode press the ON ...

Page 19: ...d is completely disconnected Attention before restarting the UPS reset the stop device The circuitry of the remote control terminal board is self powered with SELV circuits Therefore an external voltage supply is not required When a contact is closed a maximum current of 15mA circulates All connections with the remote control terminal board are made through a cable which guarantees a double insula...

Page 20: ...full display of the status of the UPS via USB or or a list of possible configurations available to the user refer to the UPS Configuration paragraph RS232 F INSTALLATION OPERATIONS 1 Connect one of the UPS s communication ports to one of the PC s communication ports using the cable supplied 2 Follow the installation instructions shown within the software manual which can be located in the UPSTools...

Page 21: ... 1 65000 sec in 1 sec steps Battery low warning Estimated autonomy time remaining for the battery low warning 3 min 1 255 min in 1 min steps Battery test Interval of time for the automatic battery test 40 hours Disabled 1 1000 h in 1 hour steps Maximum charge alarm threshold Selects the user overcharge limit Disabled Disabled 0 103 in 1 steps EnergyShare Select the auxiliary socket operating mode ...

Page 22: ... manual provided 2 TXD 3 RXD 5 GND 6 Power supply DC I 20mA max 8 Programmable output de m fault low battery pre alar 9 Programmable output default battery operation COMMUNICATION SLOT The UPS is equipped with an expansion slot for optional communication cards see figure on right which allows the device to communicate using the on standards main communicati Some examples Second RS232 and USB port ...

Page 23: ... IS VERY HEAVY USE EXTREME CAUTION WHEN REPLACING IT 1 Set the UPS to battery swap mode manually by pressing the ON SEL buttons for 4 seconds see paragraph play should show the message C02 entitled USE Configuration of Operating Mode The dis NOTE in this condition the load is powered from mains 2 The battery pack is positioned behind the UPS front panel Remove the front panel as shown in the figur...

Page 24: ...atteries see the label located on the battery pack near the connector 5 Insert the new battery pack into the compartment sliding it into the UPS Put the battery pack retention panel back in position and secure it with the two screws removed previously Connect the battery pack cable to the UPS and close the front panel Set the UPS to normal operation mode by pressing ON SEL for at least 4 seconds 6...

Page 25: ... IS NOT POWERED THE UPS IS IN STAND BY MODE Press the ON button on the front panel to power the loads NO CONNECTION TO THE LOAD Check the connection to the load THE UPS IS OPERATING FROM THE BATTERY DESPITE THE PRESENCE OF MAINS VOLTAGE THE INPUT VOLTAGE IS OUTSIDE THE PERMITTED TOLERANCE RANGE FOR MAINS OPERATION Problem with the mains Wait until the input mains voltage returns within the toleran...

Page 26: ...e THE BUZZER SOUNDS CONTINUOUSLY AND THE DISPLAY SHOWS ONE OF THE FOLLOWING CODES F04 L04 THE TEMPERATURE OF THE HEATSINKS INSIDE THE UPS IS TOO HIGH Check that the temperature of the environment in which the UPS is located does not exceed 40 C THE BUZZER SOUNDS CONTINUOUSLY AND THE DISPLAY SHOWS ONE OF THE FOLLOWING CODES F53 L53 THERE IS A FAULT ON ONE OR MORE OF THE UTILITIES POWERED BY THE UPS...

Page 27: ...mance or prevent certain functions from being used CODICE DESCRIZIONE A06 Sensor1 temperature under 0 C A08 Sensor2 temperature under 0 C A54 Load percentage greater than the user threshold set A61 Replace batteries A62 Batteries missing or Battery Box missing or not connected A63 Waiting for battery charging Alarms these are more critical problems than anomalies because if they persist they could...

Page 28: ...the load being powered by the bypass line this procedure is excluded for locks due to serious persistent overloads and short circuits CODICE DESCRIZIONE L04 Heatsink over temperature L05 Temperature sensor1 faulty L07 Temperature sensor2 faulty L11 Input relay faulty L13 Capacitor pre charge failed L20 Capacitor bank undervoltage L21 Capacitor bank overvoltage L40 Inverter overvoltage L41 Continuo...

Page 29: ...ked after 10 sec From battery locked after 5 sec Load overload 150 From mains locked after 1 sec From battery locked 0 5 sec OTHER DATA Leakage current towards ground mA 1 Room temperature 3 C 0 40 Humidity 90 without condensation Protection devices excessive battery discharge over current short circuit over voltage under voltage thermal Dimensions W x D x H 4 mm 87 x 425 x 450 87 x 625 x 450 Weig...

Page 30: ...M Battery rated voltage Vdc 72Vdc Dimensions W x D x H mm 87 x 625 x 450 Weight Kg 25 38 The symbol replaces an alphanumeric code for internal use If the UPS is connected to a battery box the maximum active power is derated from PF 0 9 to PF 0 8 ...

Page 31: ...0MNVSD1K1RUENUA ...

Reviews: