FAN SPEED CONTROL ADR 80 - 230
ADR80230_5.04_eng
Project:
ADR Regulator
Revision Doc.:5,0
Date
: 29.05.2009
Page.
5
WORKING IN PRESSURE (window visible only with this selection)
Working in PRESSURE allows the control of the condensation, evaporation pressure circuit. Working in the
pressure mode requires the input of other SETUP parameters, for a correct match with the characteristics of the
plant, from the equipment manufacturer.
Î
P R O B E T Y P E : Selects the type of sensors/transducers
(Current. 4-20 mA, Current. 0-20 mA, Voltage 0-10V)
C U R R . 4 2 0 m A
Ú
Î
P R E S S U R E M A X . Sets
the
max
value, in bar, for the sensor (for instance
could be 8 bar only when it working in low pressure).
I N
B
A
R
3
0
. 0
Ú
Î
I N P U T
V A L U E S
Defines how the data is exchanged with the software that
controls the SET of adjustment parameters: Pressure in
BAR or temperature corresponding to pressure in °C
R E G U L A T . I N
° C
Ú
Î
F R E O N F
T Y P E :
Defines the refrigerant type: R 22, R 134A,R 407C, R 507
R 404A and R410A. The software contains the graphs
and curves of refrigerants and automatically changes BAR
into °C.
F R E O N
2 2
Ú
WINDOWS FOR ANY ADJUSTMENT
Î
A U T O S T A R T
N O
If YES is set, in case of main power interruption the
regulator starts automatically.
M A I N S Y
E
S
Ú
Î
S
E
N
S
O
R
S
N
R
Defines
the
number of sensors/transducers connected. It
could be 1 or 2
T R A N S D U C E R S 1
Ú
Î
O U T P U T
P H A S E
Defines the minimum supply voltage in % for the fan.
A minimum supply voltage, for all the fans, of about 15%
of the total voltage is available.
M
I N I M
U M
0 %
Ú
Î
O U T P U T
P H A S E
Defines the maximum supply voltage of the fan in the reg-
ulated zone. Once the set point has been adjusted the fan
will operate at 100% voltage.
M A X I M U M 1
0
0
%
Ú
Î
S T A R T
1 0 0 %
Defines for each start of the fan the time between 0 – 10”
during which the fan operates at 100% supply voltage.
(Attention: 0” can create problems at fan starting).
V
O
L
T
P
E
R
0 S .
Ú
THE “END” KEY confirms the SETUP values.
S E T U P - P A R A M
E T .
SETUP parameters
Adjustment parameters
Language field
Î
R E G U L A T I O N
L A N G U A G E
4.2 SETTING OF 'ADJUSTMENT' PARAMETERS
To modify the values, use the same procedure as per SET-UP parameters.
Î
R E G U L A T I O N
Starting point of the fan. Value in BAR or °C – This is the
starting point of the fan with the MINIMUM SET VOLT-
AGE
S T A R T B
A
R
Ú
Î
R E G U L A T I O N
END of the working zone (point of MAXIMUM VOLTAGE).
Beyond this value the supply voltage to the fan is 100% of
the available voltage.
E
N
D
B
A
R
Ú
Î
R E G U L A T I O N
Ideal working point in Bar or °C.
The adjustment in PID will try to maintain this value.
S
E
T
B A R
Ú