6 Alarm Activation
5-5. How to exit
GD-D58 Series
- 36 -
6
Alarm Activation
A fault alarm is triggered when the detector head detects abnormalities. After a fault alarm is triggered, the
fault lamp (yellow) lights up and an error message is displayed on the LED. Determine the causes and take
appropriate actions.
After the detector head is successfully returned from the fault, it restarts with the process normally
performed right after it is turned on (initial clear).
If the detector head has problems and is repeatedly malfunctioning, contact RIKEN KEIKI immediately.
<Low Flow Rate Abnormal Operations>
This alarm is triggered when the output value of the low flow sensor drops below the alarm setpoint.
The alarm is auto-reset when the flow rate exceeds a certain level.
NOTE
A low flow rate abnormality can be a cause of fault alarm.
For information on malfunctions (error messages), see "9. Troubleshooting".
When a fault alarm is triggered, the indicator/alarm unit reports a sensor abnormality or fault alarm*.
* The display of an alarm depends on the indicator/alarm unit. For details, see the operating manual
of the indicator/alarm unit.
Alarm delay time (15 seconds)
FAULT lamp lights up
Alarm setpoint value
Flow sensor
output value
0
Time