2 Important Notices on Safety
2-4. Safety
Information
- 6 -
2-4. Safety Information
Necessary information for explosion proof construction of Model SD-1OX.
The Model SD-1OX is a fixed mount, continuous-monitoring detector head and provides a 4-20mA signal
which indicates the target gas reading for use by a gas monitoring controller, recording device, or
programmable controller.
There is one point of contact and works by gas warning or trouble or both by setting.
<ATEX/IECEx Specifications>
Technical Data
(Protection Method)
Flameproof enclosure “d”
(Certificate Numbers)
IECEx DEK 13.0024X
DEKRA 13ATEX0035 X
(Group)
II
(Category)
2G
(Type of Protection and Marking code)
Ex d
II
C T6
(Equipment Protection Level)
Gb
(Ambient Temperature)*
-20
C to +60
C
(Electrical Data)
Supply voltage: DC24 V
45mA
Output signal (4 to 20 mA): DC24V 22mA
Relay (Contact output): DC30V or AC250V 0.5A
(Applicable Standard)
IEC 60079-0: 2011
,
IEC 60079-1: 2007
EN 60079-0: 2012
,
EN 60079-1: 2007
(Manual Number)
PT2E-177
* The ambient temperature on explosion-proof certification is described above and it indicates the
temperature range which can maintain the explosion-proof performance and not the product performance,
see
“10-1. List of specifications” for details.
Installation
GND
Sig+
RLY
GND
Sig+
RLY
Indicator etc.
24V
Gas Detector (SD-1OX)
Hazardous Location
(Zone 1)
Nonhazardous Location
Installation Diagram
CVVS Cable
24V