4 How to Use
4-1. Before using the detector
SD-1DGH
- 12 -
CAUTION
This is a precision device. Because the detector may not provide the specified performance in some
places (environments), check the environment in the installation point, and then take appropriate
actions if necessary.
Because the detector plays an important role for safety and disaster prevention, as many units of
the detector as needed must be installed in appropriate points.
Because points where gases leak and remain easily are different depending on the types of gases
and the working areas, please decide carefully on installation points and the number of units to be
installed.
4
How to Use
4-1. Before using the detector
Not only the first-time users but also the users who have already used the product must follow the operating
precautions.
Ignoring the precautions may damage the detector, resulting in inaccurate gas detection.
4-2. Precautions for installation points
Do not install the detector in a place with vibrations or shocks.
The detector consists of sensitive electronic parts. The detector must be installed in a stable place without
vibrations or shocks and it cannot drop.
Do not install the detector in a place exposed to water, oil or chemicals.
When selecting installation points, avoid a place where the detector is exposed to water, oil or chemicals.
Do not install the detector in a place where the range of operating temperatures is exceeded.
The detector must be installed in a stable place where the operating temperature is maintained and do not
change suddenly.
<Japanese Specifications> -20 to 53
º
C
<Overseas Specifications> -20 to 60
º
C
Do not install the detector in a place exposed to direct sunlight or sudden changes in the temperature.
When selecting installation points, avoid a place where it is exposed to direct sunlight or radiant heat
(infrared rays emitted from a high-temperature object), and where the temperature changes suddenly.
Condensation may be formed inside the detector, or the detector cannot adjust to sudden changes in the
temperature.
Keep the detector (and its cables) away from noise source devices.
When selecting installation points, avoid a place where high-frequency/high-voltage devices exist.